7 Serial interface (Modbus RTU)
7.1 General
142
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
7.1.2 Serial interface A-B
The electrical connection between the master and the slaves is established
with RJ-45 cables. If multiple slaves are being used, they are connected in
parallel by using RJ-45 cables and DX-SPL-RJ45-3SL splitters.
The DC1 frequency inverter built-in RJ45 port supports the Modbus RTU pro-
tocol and therefore allows a direct network connection without an additional
interface module. The network cable must be provided at each physical end
(last station) with a bus termination resistor of 120
Ω
in order to prevent sig-
nal reflections and the resulting transfer errors.
Splitter model DX-CBL-TERM includes the required resistor mentioned
above.
Figure 83:
RJ-45 socket wiring
Pin
Meaning
1
CANopen -
2
C
3
0 V
4
RJ45 connection / external operating unit / PC connection -
5
RJ45 connection / external operating unit / PC conn
6
24 V DC power supply
7
RS485- Modbus RTU
8
RS485+ Modbus RTU
1
2
3
4
5
6
7
8
Содержание DC1-12011 Series
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...