7 Serial interface (Modbus RTU)
7.3 Operating mode Modbus RTU
150
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
Statusword
Fault word
Bit
Description
Value = 0
Value = 1
0
Drive not ready
Ready for operation (READY)
1
Stop
Running operation message (RUN)
2
Clockwise rotating field (FWD)
Anticlockwise rotating field (REV)
3
no error
Fault detected (FAULT)
4
Acceleration ramp
Frequency actual value equals setpoint value definition
5
–
Zero speed
6
Speed control deactivated
Speed control activated
7
Not used
Failure code
[hex]
Value shown on display
Description
00
StoP
Stop, ready for operation
01
OI-b
Brake chopper overcurrent
02
OL-br
Braking resistor overload
03
O-I
• Overcurrent at frequency inverter output
• Motor overload
• Overtemperature on frequency inverter heat sink
04
I_t-trP
Motor, thermal overload
05
PS-trP
Internal fault (power section)
06
O_Vo IE
Overvoltage (DC link)
07
U_Vo IE
Undervoltage (DC link)
08
O-t
Overtemperature (heat sink)
09
V-t
Overtemperature (heat sink)
0A
P-dEF
Default settings (parameters have been loaded)
C0
E-triP
external error message
0C
SC-trP
Field bus error
0D
reserved
0E
P-LOSS
Phase failure (mains side)
0F
SPIn-F
Motor pick-up control function (for catching spinning motors)
failed
10
th-Flt
Internal thermistor fault (heat sink)
11
dAtA-F
EEPROM checksum fault
12
4-20 F
Analog input:
• Out-of-range value
• Wire breakage (4-mA monitoring)
Содержание DC1-12011 Series
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...