6 Parameters
6.2 Digital and analog inputs
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
113
6.2.2.3 Two-wire control
For two-wire control, the parameters must be configured as shown in the fol-
lowing tables:
•
P-12 = 0
→
P-15 = 0, 6, 8
•
P-12 = 1 or = 2
→
P-15 = 0, 1, 5, 6, 8, 9, 10, 11, 12
•
P-12 = 5
→
P-15 = 8
Control signal terminal (P-12 = 0)
Operating unit (P-12 = 1 or P-12 = 2)
PI controller with external actual value (P-12 = 5)
P-15
DI1
DI2
DI3 / AI2
AI1 / DI4
Explanation
0
0 = Stop
1 = Run
0 = FWD
1 = REV
0 = Selected setpoint
source
1 = Fixed frequency 1
(P-20)
Setpoint value AI1
6
0 = Stop
1 = Run
0 = FWD
1 = REV
external fault:
0 = Fault
1 = Run
Setpoint value AI1
8
0 = Stop
1 = Run
0 = FWD
1 = REV
0
0
Fixed frequency 1 (P-20)
1
0
Fixed frequency 2 (P-21)
0
1
Fixed frequency 3 (P-22)
1
1
Fixed frequency 4 (P-23)
P-15
DI1
DI2
DI3 / AI2
AI1 / DI4
0, 1, 5, 8,
9, 10, 11,
12
0 = Stop
1 = Run
1 = Increase frequency
1 = Reduce frequency
0 = FWD
1 =REV
6
0 = Stop
1 = Run
0 = FWD
1 = REV
external fault:
0 = Fault
1 = Run
0 = Keypad setpoint value
1 = Fixed frequency 1
(P-20)
P-15
DI1
DI2
DI3 / AI2
AI1 / DI4
8
0 = Stop
1 = Run
0 = FWD
1 = REV
PI feedback AI
Setpoint value AI
Содержание DC1-12011 Series
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...