6.2 Digital and analog inputs
Parameter P-15 is used to configure the mode of operation and function of
both the digital and analog inputs. The configured value will depend on
parameter P-12.
Figure 58:
Digital and analog inputs
The operation of the DC1 frequency inverter via control signal terminals
(P-12 = 0, P-15 = 5) is active with default settings:
•
DI1 (control signal terminal 2): FWD (Start enable clockwise rotating
field)
•
DI2 (control signal terminal 3): REV (Start enable anti-clockwise rotating
field)
•
DI3/AI2 (control signal terminal 4): FF1 (fixed frequency 1= P-20;
DS = 15 Hz)
•
AI1/DI4 (control signal terminal 6): analog setpoint input (0 - 10 V)
When control signal terminal 2 (FWD) and control signal terminal 3 (REV) are
activated at the same time, the default configuration will activate quick stop
dec2 (P-24).
2
DI1
FWD
+24 V
3
DI2
REV
4
DI3
AI2
FF1
6
AI1
DI4
f-Soll
1
+24 V Out
< 100 mA
CPU
0...+10 V/
20 mA
P-12 = 0
DI3 AI2
AI1 DI4
P-15 = 4
P-15 = 2
P-15 = 8
P-15 = 9
Содержание DC1-12011 Series
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...