3 Installation
3.4 Electrical Installation
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
63
3.4 Electrical Installation
CAUTION
Carry out the wiring work only after the frequency inverter has
been correctly mounted and secured.
DANGER
Electric shock hazard - risk of injuries!
Carry out wiring work only if the unit is de-energized.
NOTICE
Fire hazard!
Only use cables, protective switches, and contactors that fea-
ture the indicated permissible nominal current value.
NOTICE
In DC1 frequency inverters, earth leakage currents are greater
than 3.5 mA (AC). Because of this, and as per product standard
IEC/EN 61800-5-1, an additional protective conductor must be
connected, or the cross-sectional area of the protective conduc-
tor must be at least 10 mm
2
.
DANGER
The components in the frequency inverter’s power section
remain energized up to five (5) minutes after the supply voltage
has been switched off (intermediate circuit capacitor discharging
time).
Pay attention to hazard warnings!
.
→
Complete the following steps with the specified tools and with-
out using force.
Содержание DC1-12011 Series
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...