
6 Parameters
6.2 Digital and analog inputs
108
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
6.2.1 Digital Input (DI)
Control signal terminals 2, 3, 4, and 6 can be used as digital inputs (DI). The
digital inputs‘ function and mode of operation are configured in parameter
P-15.
Example
Desired options:
•
Clockwise rotating field (FWD),
•
Anticlockwise rotating field (REV),
•
external fault,
•
Setpoint value via AI1.
Figure 59:
Example of an external fault (EXT)
Table 14:
Digital input wiring
•
DI1 (control signal terminal 2): FWD (Forward = Start enable clockwise
rotating field)
•
DI2 (control signal terminal 3): REV (Reverse = Start enable anti-clock-
wise rotating field)
•
DI3 (control signal terminal 4): external fault
•
AI1 (control signal terminal 6): analog setpoint value
P-15
DI1
DI2
DI3
AI1
7
0 = locked
1 = Start enable FWD
0 = locked
1 = Start enable REV
External fault
0 = Fault
1 = Enable
Setpoint value AI1
(0 - 10 V)
DI1 + DI2
= Quick stop (P-24)
2
DI1
FWD
+24 V
3
DI2
REV
4
DI3
EXT
6
AI1
f-Soll
1
+24 V Out
< 100 mA
0...+10 V/
20 mA
P-12 = 0
P-15 = 7
Содержание DC1-12011 Series
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...