background image

10

Instruction Booklet 

IB48050

Effective September 2012

Instructions for installation,

operation, and maintenance of the

AMPGARD 15 kV, 300A vacuum starter

eaton Corporation

 www.eaton.com

Some wiring may need to be connected to devices on the low 

voltage door or in the low voltage compartment . Wiring to these 

devices should come through one of the wire cutouts in the  

bottom left of the low voltage compartment . Confirm that there  

is sufficient slack in the wiring to allow the medium voltage door  

to open properly .
A horizontal low voltage wireway is located at the bottom front 

of each lineup . The equipment ground bus is also located in the 

wireway . This area may be used to route control wires that must 

pass from one structure to another .

Control Power Transformer

Ground Bus

Optional 

Potential 

Transformers

Figure 20. Ground Bus and CPT

Setting of adjustable protective devices

AMPGARD controllers may contain protective devices such as 

solid-state motor protection relays, overcurrent relays, incomplete 

sequence timers, and other devices critical to the proper operation 

of the starter . Due to the wide variation in job site parameters, these 

devices are not set at the factory . It is the purchaser’s responsibility 

to ensure that all adjustable devices are properly set before 

energizing the equipment . All warranty is void if adjustable devices 

are not properly set prior to initially starting the equipment .

m

 Danger

failure to properly set aDjustable Devices may result in 

equipment Damage, personal injury, or Death.

pre-startup checks

Before attempting to put a newly installed controller into  

service, study the wiring diagrams, control schematics, other  

order specific drawings, and all instruction literature . Ensure that  

all adjustable devices, including protective relays and timers, have 

been properly set .
Verify that the controller and motor are connected per the Eaton 

drawings . This is particularly essential in this class of equipment as 

the fuse ratings, current transformers, and overload protection are 

based on the characteristics of the particular motor (or other load)  

to be controlled .
Ensure that all safety precautions have been taken and that the 

installation conforms to applicable regulations and safety practices .
The equipment should be cleaned of dirt, scraps of wire, tools, 

and other foreign material . The dielectric strength of the vacuum 

interrupters should be checked before the contactor is energized 

for the first time and regularly thereafter to detect at the earliest 

possible date any deterioration in the dielectric strength of the 

interrupter, because this may result in an interruption failure . The test 

is best performed with the contactor removed from the controller 

cubicle . Removal instructions can be found later in this IB in the 

maintenance/contactor section . If testing is performed with the 

contactor installed, care must be taken to ensure that no damage 

is inflicted on the controller control power transformer, potential 

transformers, or to the controller load . Removal of the primary  

fuses is sufficient to protect the CPT or PTs . Cables to the load 

should be disconnected . Although an AC test is recommended,  

a DC test may be performed if only a DC test unit is available .  

A good vacuum interrupter will withstand a 27 kV, 60 Hz test or  

a 38 kV, DC test across the normally open contact gap . When 

performing DC tests, the voltage should be raised in discrete 

steps until the final test voltage is reached . When tested with an 

AC high potential tester, expect a capacitance leakage current of 

approximately 1 mA per interrupter . Refer to IB48051 for more 

information on dielectric testing of the vacuum interrupters .
The insulation level of the starter should be checked and recorded 

before the unit is energized .
Enclosure doors should close easily . Do not force doors closed, but 

rather look for improperly positioned contactors, isolating switches, 

or other devices .

Содержание AMPGARD

Страница 1: ...Installation 8 Handling 8 Storage 8 Mounting 8 Bus splicing 8 Power connections 8 Motor load cable termination 9 Control connections 9 Setting of adjustable protective devices 10 Pre startup checks 1...

Страница 2: ...of each controller Contained on this nameplate are the controller type and ratings as required by industry standards Also contained on this nameplate is the factory s general order number This number...

Страница 3: ...age Tripping burden 24 Vdc 48 and 96 Vdc 110 and 220 Vac 250 000 operations 24 48 96V 110 220V 50 60 Hz 80 rated coil voltage 1200 VA 400 VA 500 VA Ratings are based on full voltage starting of standa...

Страница 4: ...operated In the open position the switch isolates medium voltage from the main controller compartment allowing access to the controller for inspection and maintenance For standard applications the is...

Страница 5: ...in the isolating position See Figure 5 for location of barber poles The use of a flashlight will help in verifying the position of the barber poles Grounding Fingers 3 Barber Poles Indicating Shutter...

Страница 6: ...h the switch operating mechanism The second door must be closed before the main door is closed Both doors must be closed before the switch operator can be moved to the closed position Note N Attemptin...

Страница 7: ...Door Open Figure 12 LV Terminal Blocks LV Door Open A test plug and receptacle are typically supplied inside the low voltage section The receptacle is wired to the secondary of the controller control...

Страница 8: ...actory before shipment However vibration and mechanical stresses imposed by transit and installation can adversely affect mechanical interlocks and other adjustments therefore a final inspection is es...

Страница 9: ...shover at the load connections Motor Load Connections Figure 16 Motor Load Connections Shown With Optionally Supplied Lugs Removable Phase Barriers Figure 17 Close Up Motor Load Connections MV Conduit...

Страница 10: ...are connected per the Eaton drawings This is particularly essential in this class of equipment as the fuse ratings current transformers and overload protection are based on the characteristics of the...

Страница 11: ...d as follows Isolate and lock out all incoming power sources Open the isolation switch Open the medium voltage door Verify that the mechanical interlocks between the contactor and the handle mechanism...

Страница 12: ...ied Blown Fuse Indicator Figure 24 Blown Fuse Indicator Fuses can be removed by loosening the four nuts that secure the fuses to their mounting studs on the lower portion of the copper plate The phase...

Страница 13: ...y in both directions with an increase in resistance as the stabs engage the controller line fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove t...

Страница 14: ...bus connections checked for tightness Remove the polyester barrier mounted immediately below the switch for access to the vertical bus connections refer to Figure 33 Verify the operation of the shutte...

Страница 15: ...back of the door preventing the door from opening with the switch closed In the unlikely event the switch malfunctions and cannot be opened it will be necessary to drill out the welds to allow access...

Страница 16: ...rved Printed in USA Publication No IB48050 Z12716 September 2012 Eaton is a registered trademark of Eaton Corporation All other trademarks are property of their respective owners Instruction Booklet I...

Отзывы: