Disconnect by Removing Pin in Clevis of Drive Rod

Figure 31. Isolation Switch Drive Rod

Bolts (2) Securing Removable to Fixed Portion of Switch

Figure 32. Bolts Securing Isolation Switch

The fixed portion of the switch including the isolating shutter 

remains in the controller . Medium voltage may be present at the 

line fingers behind this shutter . 

Before attempting to inspect the 

line fingers or do other work on the fixed portion of the switch, 

ensure that the controller incoming power is isolated and 

locked out at an upstream feeder.

With the incoming power locked out, the fingers can be inspected 

and the vertical bus connections checked for tightness . Remove  

the polyester barrier mounted immediately below the switch for 

access to the vertical bus connections (refer to 

Figure 33

) . Verify  

the operation of the shutter mechanism by gently pushing it to the 

left . It should spring back to the closed position when released .

m

 Danger

failure to lock out incoming power before servicing the  

fixeD portion of the switch or the vertical bus can result  

in equipment Damage, severe injury, or Death.

Remove Barrier for Access to Vertical Bus Connections 

(incoming power must be locked out first)

Shutter

“Barber Poles” 

(3) Visible 

When Shutter 

is Closed

Figure 33. Fixed Isolation Switch

Reinstallation is the reverse of the procedure above . Verify that the 

shaft of the removable portion of the switch is rotated to the fully 

open position before reinstallation .

m

 Danger

if the switch is inserteD with the shaft in the closeD position, 

the shutter may be forceD open anD live parts may be 

contacteD, resulting in severe injury or Death.

Содержание AMPGARD

Страница 1: ...Installation 8 Handling 8 Storage 8 Mounting 8 Bus splicing 8 Power connections 8 Motor load cable termination 9 Control connections 9 Setting of adjustable protective devices 10 Pre startup checks 1...

Страница 2: ...of each controller Contained on this nameplate are the controller type and ratings as required by industry standards Also contained on this nameplate is the factory s general order number This number...

Страница 3: ...age Tripping burden 24 Vdc 48 and 96 Vdc 110 and 220 Vac 250 000 operations 24 48 96V 110 220V 50 60 Hz 80 rated coil voltage 1200 VA 400 VA 500 VA Ratings are based on full voltage starting of standa...

Страница 4: ...operated In the open position the switch isolates medium voltage from the main controller compartment allowing access to the controller for inspection and maintenance For standard applications the is...

Страница 5: ...in the isolating position See Figure 5 for location of barber poles The use of a flashlight will help in verifying the position of the barber poles Grounding Fingers 3 Barber Poles Indicating Shutter...

Страница 6: ...h the switch operating mechanism The second door must be closed before the main door is closed Both doors must be closed before the switch operator can be moved to the closed position Note N Attemptin...

Страница 7: ...Door Open Figure 12 LV Terminal Blocks LV Door Open A test plug and receptacle are typically supplied inside the low voltage section The receptacle is wired to the secondary of the controller control...

Страница 8: ...actory before shipment However vibration and mechanical stresses imposed by transit and installation can adversely affect mechanical interlocks and other adjustments therefore a final inspection is es...

Страница 9: ...shover at the load connections Motor Load Connections Figure 16 Motor Load Connections Shown With Optionally Supplied Lugs Removable Phase Barriers Figure 17 Close Up Motor Load Connections MV Conduit...

Страница 10: ...are connected per the Eaton drawings This is particularly essential in this class of equipment as the fuse ratings current transformers and overload protection are based on the characteristics of the...

Страница 11: ...d as follows Isolate and lock out all incoming power sources Open the isolation switch Open the medium voltage door Verify that the mechanical interlocks between the contactor and the handle mechanism...

Страница 12: ...ied Blown Fuse Indicator Figure 24 Blown Fuse Indicator Fuses can be removed by loosening the four nuts that secure the fuses to their mounting studs on the lower portion of the copper plate The phase...

Страница 13: ...y in both directions with an increase in resistance as the stabs engage the controller line fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove t...

Страница 14: ...bus connections checked for tightness Remove the polyester barrier mounted immediately below the switch for access to the vertical bus connections refer to Figure 33 Verify the operation of the shutte...

Страница 15: ...back of the door preventing the door from opening with the switch closed In the unlikely event the switch malfunctions and cannot be opened it will be necessary to drill out the welds to allow access...

Страница 16: ...rved Printed in USA Publication No IB48050 Z12716 September 2012 Eaton is a registered trademark of Eaton Corporation All other trademarks are property of their respective owners Instruction Booklet I...

Отзывы: