Instruction Booklet 

IB48050

Effective September 2012

Instructions for installation,

operation, and maintenance of the

AMPGARD 15 kV, 300A vacuum starter

eaton Corporation

 www.eaton.com

Ensure that all phase barriers are in good condition and are properly 

installed . Barriers are located in the isolation switch, the lower  

fuse mounts, the contactor load stab assembly, and the motor  

load stab assembly .

Phase 

Barriers 

(4)

Figure 21. Lower Fuse Mounting With Phase Barriers Installed

Verify that the contactor is fully inserted into the controller 

compartment . All finger-stab combinations must be properly 

engaged . A mounting bracket is provided to secure the contactor 

in the cell . Verify that the securing bolt is in place and properly 

tightened to the bracket . A small gap between the contactor 

baseplate and the mounting bracket is normal . Do not overtighten 

the bolt, or damage to the contactor can occur .

Hold-Down 

Hardware

Figure 22. Contactor Hold-Down Bracket

m

 Danger

all sources of meDium voltage must be isolateD anD lockeD 

out at the upstream feeDer before the interlock check can be 

performeD. failure to isolate anD lock out all incoming power 

to the lineup can result in equipment Damage, severe injury,  

or Death.

Mechanical interlocks should be checked as follows: 

Isolate and 

lock out all incoming power sources

 . Open the isolation switch . 

Open the medium voltage door . Verify that the mechanical interlocks 

between the contactor and the handle mechanism are connected 

and functioning properly . The switch drive rod connection and the 

contactor interlock rod connections should be verified by operating 

the handle mechanism, open-to-close-to-open . The door interlock 

plunger must be held in by hand during this operation . Verify that 

the pivot arm on the handle mechanism drops down and makes 

contact with the cam after the handle is fully closed . Failure to 

contact the cam may indicate a problem with the adjustment of the 

aluminum interlock arm on the contactor . Close the main contactor 

with test power and attempt to operate the switch while holding the 

door interlock plunger in . The mechanical interlock should prevent 

the switch from operating . Avoid putting excessive force on the 

operating handle during this operation or damage to the handle 

mechanism may occur . 

Verify that the door interlock plunger 

returns to its normal forward position after releasing. If the 

plunger remains in the depressed position after it is manually 

released, the interlock will not properly function to prevent 

operation of the switch with the door open.

Switch 

Drive 

Rod

Door 

Interlock 

Plunger

Pivot 

Arm

Contactor 

Interlock 

Rod

Cam

Pivot Arm Should 

Contact Cam

MV Door 

Interlock

Figure 23. Mechanical  Interlock Verification

Содержание AMPGARD

Страница 1: ...Installation 8 Handling 8 Storage 8 Mounting 8 Bus splicing 8 Power connections 8 Motor load cable termination 9 Control connections 9 Setting of adjustable protective devices 10 Pre startup checks 1...

Страница 2: ...of each controller Contained on this nameplate are the controller type and ratings as required by industry standards Also contained on this nameplate is the factory s general order number This number...

Страница 3: ...age Tripping burden 24 Vdc 48 and 96 Vdc 110 and 220 Vac 250 000 operations 24 48 96V 110 220V 50 60 Hz 80 rated coil voltage 1200 VA 400 VA 500 VA Ratings are based on full voltage starting of standa...

Страница 4: ...operated In the open position the switch isolates medium voltage from the main controller compartment allowing access to the controller for inspection and maintenance For standard applications the is...

Страница 5: ...in the isolating position See Figure 5 for location of barber poles The use of a flashlight will help in verifying the position of the barber poles Grounding Fingers 3 Barber Poles Indicating Shutter...

Страница 6: ...h the switch operating mechanism The second door must be closed before the main door is closed Both doors must be closed before the switch operator can be moved to the closed position Note N Attemptin...

Страница 7: ...Door Open Figure 12 LV Terminal Blocks LV Door Open A test plug and receptacle are typically supplied inside the low voltage section The receptacle is wired to the secondary of the controller control...

Страница 8: ...actory before shipment However vibration and mechanical stresses imposed by transit and installation can adversely affect mechanical interlocks and other adjustments therefore a final inspection is es...

Страница 9: ...shover at the load connections Motor Load Connections Figure 16 Motor Load Connections Shown With Optionally Supplied Lugs Removable Phase Barriers Figure 17 Close Up Motor Load Connections MV Conduit...

Страница 10: ...are connected per the Eaton drawings This is particularly essential in this class of equipment as the fuse ratings current transformers and overload protection are based on the characteristics of the...

Страница 11: ...d as follows Isolate and lock out all incoming power sources Open the isolation switch Open the medium voltage door Verify that the mechanical interlocks between the contactor and the handle mechanism...

Страница 12: ...ied Blown Fuse Indicator Figure 24 Blown Fuse Indicator Fuses can be removed by loosening the four nuts that secure the fuses to their mounting studs on the lower portion of the copper plate The phase...

Страница 13: ...y in both directions with an increase in resistance as the stabs engage the controller line fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove t...

Страница 14: ...bus connections checked for tightness Remove the polyester barrier mounted immediately below the switch for access to the vertical bus connections refer to Figure 33 Verify the operation of the shutte...

Страница 15: ...back of the door preventing the door from opening with the switch closed In the unlikely event the switch malfunctions and cannot be opened it will be necessary to drill out the welds to allow access...

Страница 16: ...rved Printed in USA Publication No IB48050 Z12716 September 2012 Eaton is a registered trademark of Eaton Corporation All other trademarks are property of their respective owners Instruction Booklet I...

Отзывы: