Instruction Booklet 

IB48050

Effective September 2012

Instructions for installation,

operation, and maintenance of the

AMPGARD 15 kV, 300A vacuum starter

eaton Corporation

 www.eaton.com

Vacuum contactor

300A, 15 kV AMPGARD medium voltage controllers are supplied  

with 300A vacuum contactors . The contactor has an interrupting 

rating of 5000A and is open-rated to carry 300A continuously .  

The contactor enclosed rating is also 300A .

Figure 9. 300A, 15 kV SL Vacuum Contactor

Contactors are typically three-pole devices except in the case of the 

start contactors on autotransformer starters, which are normally 

two-pole devices .
Refer to Instruction Book IB48051 for further details on the operation 

and maintenance of the vacuum contactors .
Controllers supplied as transformer feeders or for other specialized 

applications are sometimes supplied with contactors that include 

a mechanical latch device . Refer to Eaton for further details on the 

operation and maintenance of the latch mechanism .

Safety interlocks

AMPGARD controllers are manufactured with several built-in 

interlock provisions and safety features to reduce hazards and 

provide proper operating sequences .
A mechanical interlock prevents opening the medium voltage door 

with the switch in the closed position . Ensure that the medium 

voltage door is fully closed and latched using the two latches on the 

right side of the door to prevent damage to the interlock bracket on 

the back of the door .
An additional interlock prevents closing of the switch unless the 

medium voltage door is closed (see MV door interlock plunger  

in 

Figure 10

) . On controllers that require two structures (reduced 

voltage starters for example), the door to the second structure 

will also be interlocked with the switch operating mechanism . The 

second door must be closed before the main door is closed . Both 

doors must be closed before the switch operator can be moved to 

the closed position .

otee:

N

Attempting to close the switch with the door open can cause damage 

to the operating mechanism .

Isolation 

Switch 

Drive Rod

MV Door Hold-Down Interlock

Contactor 

Interlock 

Rod

MV Door 

Interlock 

Plunger

Pilot Hole 

for Creating 

Optional 

Provision to 

Lock Switch 

Closed

Padlocking 

Provisions 

(Switch 

Open) 

Figure 10. Handle Mechanism with Contactor and Door Interlocks

Mechanical and electrical interlocks are provided to insure that the 

non-loadbreak isolation switch cannot be opened or closed unless 

the main contactor is de-energized (see contactor interlock rod in 

Figure 10

) . Do not attempt to force the switch operating mechanism 

with the main contactor closed . The handle mechanism is designed 

to fail before the isolation switch can be opened with the main 

contactor closed .

m

 caution

applying excessive force to the switch hanDle with the 

mechanical interlocks engageD will result in Damage to  

the switch.

An electrical interlock is provided to disconnect the control power 

transformer secondary before the isolating switch stabs are 

disconnected from the controller line fingers . This interlock ensures 

that the switch is breaking transformer magnetizing current only .  

Do not connect additional loads to the controller isolating switch .

m

 Danger

if loaDs greater than the interrupting rating of the switch 

are connecteD to the switch, equipment Damage, personal 

injury, or Death may occur.

An optional key interlock may be provided to lock the switch in the 

open position for special configurations . Refer to the specific order 

drawings to determine if key interlocks have been provided .
On reversing, two-speed or autotransformer type starters, 

mechanical interlocks are provided to prevent two or more 

contactors from closing at the same time .

Содержание AMPGARD

Страница 1: ...Installation 8 Handling 8 Storage 8 Mounting 8 Bus splicing 8 Power connections 8 Motor load cable termination 9 Control connections 9 Setting of adjustable protective devices 10 Pre startup checks 1...

Страница 2: ...of each controller Contained on this nameplate are the controller type and ratings as required by industry standards Also contained on this nameplate is the factory s general order number This number...

Страница 3: ...age Tripping burden 24 Vdc 48 and 96 Vdc 110 and 220 Vac 250 000 operations 24 48 96V 110 220V 50 60 Hz 80 rated coil voltage 1200 VA 400 VA 500 VA Ratings are based on full voltage starting of standa...

Страница 4: ...operated In the open position the switch isolates medium voltage from the main controller compartment allowing access to the controller for inspection and maintenance For standard applications the is...

Страница 5: ...in the isolating position See Figure 5 for location of barber poles The use of a flashlight will help in verifying the position of the barber poles Grounding Fingers 3 Barber Poles Indicating Shutter...

Страница 6: ...h the switch operating mechanism The second door must be closed before the main door is closed Both doors must be closed before the switch operator can be moved to the closed position Note N Attemptin...

Страница 7: ...Door Open Figure 12 LV Terminal Blocks LV Door Open A test plug and receptacle are typically supplied inside the low voltage section The receptacle is wired to the secondary of the controller control...

Страница 8: ...actory before shipment However vibration and mechanical stresses imposed by transit and installation can adversely affect mechanical interlocks and other adjustments therefore a final inspection is es...

Страница 9: ...shover at the load connections Motor Load Connections Figure 16 Motor Load Connections Shown With Optionally Supplied Lugs Removable Phase Barriers Figure 17 Close Up Motor Load Connections MV Conduit...

Страница 10: ...are connected per the Eaton drawings This is particularly essential in this class of equipment as the fuse ratings current transformers and overload protection are based on the characteristics of the...

Страница 11: ...d as follows Isolate and lock out all incoming power sources Open the isolation switch Open the medium voltage door Verify that the mechanical interlocks between the contactor and the handle mechanism...

Страница 12: ...ied Blown Fuse Indicator Figure 24 Blown Fuse Indicator Fuses can be removed by loosening the four nuts that secure the fuses to their mounting studs on the lower portion of the copper plate The phase...

Страница 13: ...y in both directions with an increase in resistance as the stabs engage the controller line fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove t...

Страница 14: ...bus connections checked for tightness Remove the polyester barrier mounted immediately below the switch for access to the vertical bus connections refer to Figure 33 Verify the operation of the shutte...

Страница 15: ...back of the door preventing the door from opening with the switch closed In the unlikely event the switch malfunctions and cannot be opened it will be necessary to drill out the welds to allow access...

Страница 16: ...rved Printed in USA Publication No IB48050 Z12716 September 2012 Eaton is a registered trademark of Eaton Corporation All other trademarks are property of their respective owners Instruction Booklet I...

Отзывы: