background image

8

Instruction Booklet 

IB48050

Effective September 2012

Instructions for installation,

operation, and maintenance of the

AMPGARD 15 kV, 300A vacuum starter

eaton Corporation

 www.eaton.com

Main bus

AMPGARD lineups are typically supplied with copper main bus . The 

bus is located in a 12-inch high bus compartment mounted at the top 

of the lineup . Bus may be rated 1000, 1200, or 2000A . The standard 

bus is insulated and tin-plated . Optional silver plating is available .  

Bus specifications can be found on the job specific order drawings .

Main  

Bus

Front

LV  

Conduit 

Space

MV  

Conduit 

Space

Vertical 

Bus

Figure 15. Main Bus Compartment, Top View

The main bus compartment in a starter section includes vertical  

bus drops to connect the starter(s) to the main bus . Also included 

are wireways for routing of motor load and control cables to the 

starters below .

installation

Handling

An AMPGARD controller is insulated for high voltages and must be 

protected against damage during handling . The controller should 

remain in an upright position at all times .
Exercise extreme care during any movement and placement 

operations to prevent dropping or unintentional rolling or tipping . 

AMPGARD medium voltage equipment may be moved by forklift, 

rollers, or overhead crane .
A forklift is usually the most convenient method of handling the 

controller . Use safety straps around the protective packaging 

material when handling the controller with a forklift . Insert the forks 

under the shipping skid . Do not allow the end of the forks to enter 

the bottom of the enclosure .
Rod or pipe rollers provide a simple method for moving the controller 

on a level floor . The bottom of the AMPGARD structure is designed 

to be rolled without damage on minimum 2-inch diameter rollers, 

four rollers per 36-inch section .
AMPGARD controllers are shipped with two steel lifting angles, 

one in front and one in back, running the full width of the shipping 

section . Back-to-back units also have one in the back and one in 

the front, running the full width of the shipping section . Select or 

adjust the rigging lengths to compensate for any unequal distribution 

of the load, and maintain the controller in an upright position . 

Some controller interiors may contain heavy equipment, such as 

transformers, that can make the center of gravity vary considerably 

from the center of the lineup . 

Do not allow the angle between 

the lifting cables and vertical to exceed 45 degrees.

 Do not pass 

ropes or cables through the lift holes . Use slings with safety hooks 

or shackles, of adequate load rating .

m

 caution

each controller is properly aDjusteD at the factory before 

shipment. however, vibration anD mechanical stresses 

imposeD by transit anD installation can aDversely affect 

mechanical interlocks anD other aDjustments; therefore, 

a final inspection is essential before energizing. if this 

inspection reveals any portion of the controller has come 

out of aDjustment, the controller shoulD be re-aDjusteD 

accorDing to information in this instruction book or by a 

qualifieD eaton service engineer.

Storage

If it is necessary to store an AMPGARD controller before installation, 

keep it in a clean, dry location with ample air circulation and heat to 

prevent condensation . Like all electrical apparatus, an AMPGARD 

controller contains insulation that must be protected against dirt  

and moisture .

Mounting

AMPGARD controllers should be installed on a non-combustible level 

surface of sufficient strength to properly support the controller’s 

mass . After the lineup has been placed in position, anchor bolts  

may be installed and tightened . Refer to the job specific order 

drawings for the bolt locations . The use of 1/2-inch diameter bolts 

is recommended .
Equipment located in certain seismic zones must be anchored to 

meet the requirements of those zones . Refer to Eaton I .B . 48042 for 

instructions on mounting in these special locations . It is the user’s 

responsibility to ensure the mounting pad is sufficiently strong to 

properly anchor and support the equipment .
When an order includes two or more shipping sections, the order 

outline drawing will show the sequence in which the sections are 

to be lined up and which shipping splits are to be joined . A busbar 

splice kit and a connecting hardware kit are supplied for each open 

joint between sections .
Place the first shipping split into position . Move the second  

shipping split into position alongside the first and use the six or  

eight 3/8 x 1 .50 inch bolts and companion hardware to connect the 

two sideplates . Place one flat washer under the bolt head and one 

flat washer and one lock washer under the nut . Tighten each bolt  

to 25 lb-ft (33 Nm) .

Bus splicing

Connect the busbars using the splice kit, including hardware  

(3/8-inch diameter) that is provided with the equipment . Tighten  

bolts to 25 lb-ft (33 Nm) .

Power connections

Incoming power connects to the lineup in a variety of ways . Cables, 

bus from other close-coupled equipment, busduct, and transformer 

shunts are some of the more common methods . Note that these 

connections may be energized even when the starter isolation 

switch or other switching devices are in the open position .

m

 Danger

De-energize anD lock out all incoming power connections 

at their source before servicing any part of the equipment 

Directly connecteD to the incoming power incluDing main 

horizontal bus, vertical bus, bus potential transformers,  

or control power transformers.

Содержание AMPGARD

Страница 1: ...Installation 8 Handling 8 Storage 8 Mounting 8 Bus splicing 8 Power connections 8 Motor load cable termination 9 Control connections 9 Setting of adjustable protective devices 10 Pre startup checks 1...

Страница 2: ...of each controller Contained on this nameplate are the controller type and ratings as required by industry standards Also contained on this nameplate is the factory s general order number This number...

Страница 3: ...age Tripping burden 24 Vdc 48 and 96 Vdc 110 and 220 Vac 250 000 operations 24 48 96V 110 220V 50 60 Hz 80 rated coil voltage 1200 VA 400 VA 500 VA Ratings are based on full voltage starting of standa...

Страница 4: ...operated In the open position the switch isolates medium voltage from the main controller compartment allowing access to the controller for inspection and maintenance For standard applications the is...

Страница 5: ...in the isolating position See Figure 5 for location of barber poles The use of a flashlight will help in verifying the position of the barber poles Grounding Fingers 3 Barber Poles Indicating Shutter...

Страница 6: ...h the switch operating mechanism The second door must be closed before the main door is closed Both doors must be closed before the switch operator can be moved to the closed position Note N Attemptin...

Страница 7: ...Door Open Figure 12 LV Terminal Blocks LV Door Open A test plug and receptacle are typically supplied inside the low voltage section The receptacle is wired to the secondary of the controller control...

Страница 8: ...actory before shipment However vibration and mechanical stresses imposed by transit and installation can adversely affect mechanical interlocks and other adjustments therefore a final inspection is es...

Страница 9: ...shover at the load connections Motor Load Connections Figure 16 Motor Load Connections Shown With Optionally Supplied Lugs Removable Phase Barriers Figure 17 Close Up Motor Load Connections MV Conduit...

Страница 10: ...are connected per the Eaton drawings This is particularly essential in this class of equipment as the fuse ratings current transformers and overload protection are based on the characteristics of the...

Страница 11: ...d as follows Isolate and lock out all incoming power sources Open the isolation switch Open the medium voltage door Verify that the mechanical interlocks between the contactor and the handle mechanism...

Страница 12: ...ied Blown Fuse Indicator Figure 24 Blown Fuse Indicator Fuses can be removed by loosening the four nuts that secure the fuses to their mounting studs on the lower portion of the copper plate The phase...

Страница 13: ...y in both directions with an increase in resistance as the stabs engage the controller line fingers Inspect for any signs of mechanical wear or overheating To withdraw the removable portion 1 Remove t...

Страница 14: ...bus connections checked for tightness Remove the polyester barrier mounted immediately below the switch for access to the vertical bus connections refer to Figure 33 Verify the operation of the shutte...

Страница 15: ...back of the door preventing the door from opening with the switch closed In the unlikely event the switch malfunctions and cannot be opened it will be necessary to drill out the welds to allow access...

Страница 16: ...rved Printed in USA Publication No IB48050 Z12716 September 2012 Eaton is a registered trademark of Eaton Corporation All other trademarks are property of their respective owners Instruction Booklet I...

Отзывы: