~ 48 ~
Chapter 8 System Maintenance
NOTE
Make sure that the inverter has been powered off before the maintenance.
During operation on the inverter, use the personal protective device.
8.1 Daily maintenance of inverter
Content
Method
Frequency
System
cleanness
Check the heat sink and air inlet/outlet for foreign
bodies and dust.
Once/half a year ~once/
year
DC switch
Turn the DC switch on and off for 10 consecutive
times to ensure that the functions of the DC switch
are normal.
Once/ year
Electrical
connection
Turn the DC switch on and off for 10 consecutive
times to ensure that the functions of the DC switch
are normal.
Once/half a year ~once/
year
Air-tightness
Check whether the sealing of the cable inlet meets
the requirements. If the gap is too large or is not
sealed, plug it again.
Once/ year
8.2 Maintenance of inverter unused for long term
If the inverter has been not used for more than 7 days, turn off the AC input, PV input, and
battery input switches.
If the inverter has not been used for more than 3 months, turn on the AC input switch (or PV
switch) and the battery switch to start the system to recharge the battery once.
8.3 Powering off inverter
DANGER
Before the maintenance of the inverter, power it off. The hot-line work on the inverter may
cause inverter damage or electric shock.
After the inverter is powered off, it takes a certain period of time for the internal
components to discharge. Wait until the inverter is fully discharged according to the time
requirements on the label.
Step 1: Disconnect the ON-GRID AC circuit breaker of the inverter.
Step 2: Disconnect the BACK-UP AC circuit breaker of the inverter.
Step 3: Disconnect the energy storage circuit breaker between the inverter and the battery.
Step 4: Turn off the DC switch of the inverter.