Mode
Asserted by Shorting Terminals
on Inverter
Switch Operation on External DRED
DRM0
R & C
Close S1 and S5
DRM1
D1/5&C
Close S1
DRM2
D2/6&C
Close S2
DRM3
D3/7&C
Close S3
DRM4
D4/8&C
Close S4
DRM5
D1/5&R
Close S5
DRM6
D2/6&R
Close S6
DRM7
D3/7&R
Close S7
DRM8
D4/8&R
Close S8
Ripple Control: In Germany, the grid company uses the Ripple Control Receiver to convert the
grid dispatching signal and send it as a dry contact signal. Wiring of the ripple control receiver
dry contact cables is shown in the figure below.
Boot/Shutdown: Tap Boot/Shutdown to send the boot/shutdown instruction to the inverter. For
Australia and New Zealand, when the DRM state is DRM0, the "Boot" option will be prohibited.
Date Setting/Time Setting: The correct system time is very important. Wrong system time will
directly affect the data logging and power generation value. The clock is in 24-hour format.
Software Version: Version information of the current firmware.
RS485
: Used to connect to the upper computer. (Baud rate is set to 9600 in the communication
setting column on the screen.). Connect the RS485 cable A and cable B to pin 5 and pin 4 of
the RJ45 registered jack respectively, and the registered jack to the RS485 port on the housing.