Chapter 5 Installation
5.1 Preparation before installation
5.1.1 Installation environment requirements
The ambient temperature should be between -25
℃
and +60
℃
, and the relative humidity
should be between 0% and 90% (no condensation).
The inverter can be installed indoors or outdoors dry and well ventilated environment
without excessive dust, but not in direct sunlight or near heating equipment.
The inverter may generate noise (25dB or less) during operation. Please install the
inverter far away from the rest area.
The inverter should be installed on firm bearing surface, and installation location and
method must fit with the weight and dimension of the inverter.
The inverter should be installed vertically or at not more than 15° backward tilt, and must
not be installed at frontward tilt, or diagonally and horizontally.
During installation of the inverter, the display panel should be aligned with line of sight to
facilitate the operation.
The wiring terminals should be protected by the waterproof cover and tightened.
The inverter should be installed at less than 4000m altitude.
The inverter should be installed away from high-intensity magnetic field to avoid
electromagnetic interference. If there is a radio station or less than 30MHz wireless
telecom equipment nearby the installation site, the inverter should be installed as
following:
1.
Add a ferrite core with multi-turn winding or low pass EMI filter for the DC input
cable or AC output cable of the inverter.
2.
The inverter should be more than 30m from the wireless electromagnetic
interference equipment.
-25
℃
to +60
℃
ambient temperature,
0%-90% relative humidity (non-condensing)
Outdoor installation allowed , kept away
from direct sunlight