Chapter 6 Electrical Connection
NOTE
1.
Before installation and use of the inverter, a conductor with lug (4-6 mm2) must be used
for special protective earthing.
2.
Load capacity of BACK-UP output end of inverter is as follows:
1)
Inductive load (such as air conditioning, washing machine, motor, etc.): 6KVA
maximum total power of inductive load.
2)
Capacitive load (such as computer, switching power supply, etc.): 6KVA maximum
total power of capacitive load.
3.
It is required for the above load capacity to connect the system with the grid or provide
the battery with enough capacity. If the power is supplied only by PV, largest single
off-grid load is generally less than 2KW.
No.
Component
Description
1
PV String
The PV string consists of PV component string
2
Inverter
Support EAHI-6000-SL-S series inverter
3
Battery
The battery matching with the inverter
4
Battery Breaker
Stacking type with the energy storage switch
5
AC Circuit
Breaker
For same model, the circuit breaker of the BACK-UP load
should have same specification with the circuit breaker of
ON-GRID load. The user is recommended to buy the AC
switch.
Ensure that BACK-UP port load continuously operates
during stop of the inverter for maintenance. It is
6
Single-Pole
Double-Throw
Switch