~ 32 ~
the inverter is in grid-tied mode, the built-in ON-GRID relay is in closed state.
After the inverter is powered on, there is current at the BACK-UP AC port. If it is required
to maintain the BACK-UP load, power off the inverter; otherwise, electric shocks may be
caused.
6.3.1 N and PE cables are connected together in the Main Panel for wiring
For Australia, New Zealand and South Africa, the neutral cable of ON-GRID side and BACK-UP
side must be connected together. Otherwise BACK-UP function will not work.
NO.
Description
1
≤63A/230V/400V AC breaker
2
32A/230V/400V AC breaker
3
Depends on loads
4
Depends on household loads and inverter capacity
5
30mA RCD (Comply with local regulation)
6
30mA RCD (Comply with local regulation)
Note 1:If the battery is integrated with a readily accessible internal DC breaker, no additional
DC breaker is required.
Note 2:The recommended values in the table are for reference only. The actual values must
comply with local standard and actual conditions.
Note 3:The rated current of breaker
①
is suggested to lower than that of breaker
④
.
Note 4:If the rated current of on-site power cables are lower than those recommended above,
the breakers specification should be considered to match the power cables in first
priority.
Note 5:The AC port takes power from the grid and is set according to the grid circuit breaker.