22
The current configuration of the SCS200 can be queried via a proprietary A message.
PGN 61184 – Proprietary A
Transmission Rate:
N/A (only Rx)
Data Length:
8 bytes
Data Page:
0
PDU format
239
PDU Specific:
Destination Address (SCS200 node address)
Default Priority:
6
Parameter Group Number: 61184 (EF00h)
CAN-ID: 0x18EFxxyy
xx node address SCS200
yy: optional source address of sender
Overview set-up CAN data
The SCS200 responds to the requirement of a configuration query with the following four Proprietary B messages which reflect the
configuration values stored in the EEPROM.
PGN 65296 – Proprietary B
Transmission Rate:
as requested by the user, max. 100 ms
Data Length:
8 bytes
data page
0
PDU format
255
PDU Specific:
16
Default Priority:
6
Parameter Group Number: 65296 (FF10h)
CAN-ID: 0x18FF10xx
xx Node address SCS200
CAN data
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Contents
Message ID and
manufacturer ID
Manufacturer ID
requirement
not used
not used
not used
not used
not used
Unit
–
–
–
–
–
–
–
–
Byte
Bit
Description
Value
Byte 1
bits 8-5
message ID status and diagnosis
0x3
bits 4-1
manufacturer ID part 1
0x3
Byte 2
manufacturer ID part 2
0xD8
Byte 3
query configuration data
0x02
Byte 4
not used
0x00
Byte 5
not used
0x00
Byte 6
not used
0x00
Byte 7
not used
0x00
Byte 8
not used
0x00