20
7.4.1.4 Deactivation of fast disconnection trip 2
CAN data
7.4.1.5 Default configuration
CAN data
In order to return to the default setting, a waiting period of at least 3 seconds is required after sending the corresponding
CAN message, followed by the reset of the module.
The delay period to be adjusted per channel is calculated according to the following scheme:
basic delay (s)
X
multiplier (0 – 10)
=
delay periods (s)
Coding the basic delay within the CAN message
Value
0x0
0x1
0x2
0x3
0x4
0x5
0x6
0x7
ON delay / OFF delay (s)
0.5
1
5
10
50
100
500
1000
Byte
Bit
Description
Value
Byte 1
bits 8 – 5
message ID configuration
0x6
bits 4 – 1
manufacturer ID part 1
0x3
Byte 2
manufacturer ID part 2
0xD8
Byte 3
setting of fast disconnection
0x05
Byte 4
output channel
0x01…0x0C
Byte 5
activate / deactivate fast disconnection
0x00 (trip 2 active, default)
0x01 (trip 2 deactivated)
Byte 6
not used
0x00
Byte 7
not used
0x00
Byte 8
not used
0x00
Byte
Bit
Description
Value
Byte 1
bits 8 – 5
message ID configuration
0x6
bits 4 – 1
manufacturer ID part 1
0x3
Byte 2
manufacturer ID part 2
0xD8
Byte 3
reset to default configuration
0x04
Byte 4
not used
0x00
Byte 5
not used
0x00
Byte 6
not used
0x00
Byte 7
not used
0x00
Byte 8
not used
0x00