8.2.2 SCS200-RC08-…
Derating was determined with the following population:
Fuses
30 A channels: 40 A fuse by ESKA/MTA (p/n 340.035)
10 A channels: 15 A fuse by ESKA/MTA (p/n 340.029)
Relays 12 VDC:
30 A channels: ESR10-NC2A4HB-00-D1-30A by E-T-A
10 A channels: ESR10-NC2A4HB-00-D1-10A by E-T-A
Relays 24 VDC:
30 A channels: V23074-A2002-A403 by TE connectivity
10 A channels: channel 5-8: ESR10-NC2A4HB-00-D2-10A by E-T-A
Fig. 11 shows the derating of the max. total current of the relay version over the
ambient temperature.
fig. 11: Derating of max. total current (SCS200- RC08-...)
fig. 12: Derating of the ampacity per channel,
at max. total current (SCS200- RC08-..., 12 VDC)
Fig. 12 shows the derating of the ampacity per load output at max. total current for 12 VDC.
The ampacity of the single channels can be increased by a reduced total current.
ampacity per channel [
A
]
total
curr
ent
[ A
]
ambient temperature [ ºC ]
channel 1-4
channel 5-8
ambient temperature [ ºC ]