32
PGN 65281 – Proprietary B
Transmission Rate:
N/A (only Rx)
Data Length:
8 bytes
Data Page:
0
PDU format
255
PDU Specific:
Destination Address (SCS200 node address)
Default Priority:
6
Parameter Group Number: 65281 (FF01h)
CAN-ID 0x18FF01yy
yy: optional source address of sender
Overview set-up CAN data
7.4.3.4 Deactivate SCS200-RC… status LED
PGN 61184 – Proprietary A
Transmission Rate:
N/A (only Rx)
Data Length:
8 bytes
Data Page:
0
PDU format
239
PDU Specific:
Destination Address (SCS200 node address)
Default Priority:
6
Parameter Group Number: 61184 (EF00h)
CAN data
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Contents
Message ID and
manufacturer ID
Manufacturer ID
requirement
not used
not used
not used
not used
broadcast
Unit
–
–
–
–
–
–
–
–
Byte
Bit
Description
Value
Byte 1
bits 8 – 5
message ID status and diagnosis
0x3
bits 4 – 1
manufacturer ID part 1
0x3
Byte 2
manufacturer ID part 2
0xD8
Byte 3
Activate sleep mode
0x01
Byte 4
not used
0x00
Byte 5
not used
0x00
Byte 6
not used
0x00
Byte 7
not used
0x00
Byte 8
broadcast
0x33
CAN-ID 0x18EFxxyy
xx node address SCS200
yy: optional source address of sender