UPR700 Microprocessor-Based Pressure/Process Indicator
27
the lower display changes to
DSP.FL
. Using the
▼
or
▲
keys, select the amount of filtering desired,
from none
(OFF)
to five seconds. When finished, press the
FUNC
key to lock in the value and
advance to the next parameter.
NOTE:
The parameter group legends of instruments manufactured prior to January 1998 refer to the
primary input as “Pressure”, and the secondary input as “Temperature” regardless of the
actual process variable being indicated. When asked in the menu to “Link” an alarm to an
input. “Pressure” is always the main input (upper display), and “Temperature” is always the
secondary input (lower display).
Fig. 5
Parameter Table
Group #
Function
Mnemonic
Choices
Default
Value
Group 5
Primary Input Selection
PI.TYP
Str, 0-20, 4-20, 0-5, 0-10
Str
Group 5
Secondary Input Selection
SI.TYP
OFF, tc, rtd, 0-20, 4-20, 0-10
Tc
Group 4
Shunt Calibration
SHUNT
OFF,On
On
Group 4
Shunt Value
SHNT%
40.0 TO 100.0%
80.0%
Group 3
Input Full Scale Value
PI.FSV
10 TO 99.950
10000
Group 3
Input Low Scale Value
PI.LSV
±
25% OF SFV OF FS V
0
Group 3
Input Decimal Point Position
PI.DP
None, 1,2,3,4 places
None
Group 3
Secondary Input T/C Type
Sl.TC
tc J, tc CA, tc L, tc n
tc J
Group 3
Alarm I Input Channel Link
AI.LNK
OFF, Prl.ln, Sec.ln
Prl.ln
Group 3
Alarm I Type
AI.TYP
HI, LO, lnhib
HI
Group 3
Alarm 2 Input Channel Link
A2.LNK
OFF, Prl.ln, Sec.ln
PrLIn
Group 3
Alarm 2 Type
ALTYP
HI, 10, lnhib
HI
Group 2
Zero Calibration
ZERO.C
OFF, On, CLEAr
OFF
Group 2
Span Calibration
SPAN.C
OFF, On, CLEAr
OFF
Group 1
Alarm I Threshold
AL1
TO 110%of span
40% of range
of related input
Group 1
Alarm 2 Threshold
AL2
TO 110% of span
60% of range
of related input
In this example, these are functions necessary to allow operation of a pressure/temperature indicator
with two high alarms.
8.4
P
RIMARY
I
NPUT
S
ETUP
8.4.1 S
ETTING
THE
P
RIMARY
I
NPUT
T
YPE
FOR
A
S
TRAIN
G
AGE
T
RANSDUCER
If using a
Dynisco
transducer, the model number of the transducer will designate its own electrical
output. For example, in plastic melt applications, the PT462E-5M-6/18 or TPT432A-10M-6/18 have
a strain gage (0-3.33 mV/V dc full scale) signal output. Amplified units have a number where the
strain gage units have a letter (E or A). The PT4624-5M-6/18 has a 4-20 mA signal output; the
PT4625-5M-6/18 has a 0-5 Vdc signal output, while PT4626-5M-6/18 has a 0-10 Vdc signal output.
Содержание UPR700
Страница 14: ...14 Fig 2 Model UPR700 Outline Drawing...
Страница 16: ...16 Fig 3 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Primary Input...
Страница 33: ...UPR700 Microprocessor Based Pressure Process Indicator 33 Fig 10 Secondary Input Jumper Location...
Страница 67: ...NOTES...
Страница 68: ...NOTES...
Страница 70: ...DYNISCO LLC 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...
Страница 71: ......