UPR700 Microprocessor-Based Pressure/Process Indicator
11
the following functions:
•
alarm reset
•
remove zero calibration
•
peak reset
•
alarm, peak, and zero calibration
•
alarm and peak reset
NOTE:
This input is not isolated from primary input. A double or reinforced insulation between
instrument output and power supply must be guaranteed by the external device.
2.8
A
LARMS
S
PECIFICATION
Alarm Outputs:
2 standard alarms (AL1 and AL2). 1 optional alarm (AL3).
AL1 and AL2 Contacts:
1 SPDT 2 A max 0 240V AC resistive load.
AL3 Contacts:
1 SPST solder jumper selectable NO/NC 2 A max @ 240V AC resistive load.
Contact Protection:
Varistor for spike protection.
Alarm Type:
Each alarm is keyboard programmable for:
•
Primary / Secondary input
•
High / Low / Low inhibited on start up
•
Auto / Manual reset
Excitation Type:
Keyboard configurable for each alarm: relay coil energized in no alarm condition
(failsafe) or relay coil energized in alarm condition (non-failsafe).
Threshold:
From 0 to 110% Full Scale (the threshold may be limited due to the selected full scale
value).
Hysteresis:
Keyboard programmable for each alarm; from 0.1% to 10.0% of span or 1 LSD
(whichever is greater) for each alarm.
Filter:
Selectable from the following values for each alarm:
OFF, 0.4 s, 1 s, 2 5. 3 s. 4 s, 5 s.
Alarm Update Time:
At every input conversion.
2.9
O
PTIONAL
S
ERIAL
C
OMMUNICATION
I
NTERFACE
S
PECIFICATION
Serial Interface:
RS-485 type. Opto-isolated.
Protocol Type:
Modbus/Jbus (RTU mode).
Type of Parameters:
Run-time and configuration are available by serial link.
Содержание UPR700
Страница 14: ...14 Fig 2 Model UPR700 Outline Drawing...
Страница 16: ...16 Fig 3 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Primary Input...
Страница 33: ...UPR700 Microprocessor Based Pressure Process Indicator 33 Fig 10 Secondary Input Jumper Location...
Страница 67: ...NOTES...
Страница 68: ...NOTES...
Страница 70: ...DYNISCO LLC 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...
Страница 71: ......