Range:
nodbS, JbuS. Modbus/Jbus selection.
Default value:
Modbus.
COMMUNICATION TYPE - Group 3
Available:
Only if SC.ADR is different than Off.
Upper display: Number of bits.
Lower display: SC.FRM
Range:
8, 8 E, 8 O. 8 bit without parity, 8 bit + even parity, 8 bit + odd parity.
Default value:
8 bit without parity.
COMMUNICATION BAUD RATE - Group 3
Available:
Only if SC.ADR is different than Off.
Upper display: Baud rate.
Lower display: SC.BDR
Range:
600, 1200, 2400, 4800, 9600, 19200.
Default value:
19200.
LOADING DEFAULT DATA - Group 3
Available:
Only if access to level 3 is allowed.
Upper display: OFF
Lower display: DEFLT
Range:
Use
▼
▲
keys to switch the upper display from OFF to On 3, then press FUNC key
to load the default data of the parameters belonging to group 1, group 2, group 3.
12.4
G
ROUP
4 D
EFAULT
P
ARAMETERS
SHUNT CALIBRATION - Group 4
Available:
Always
Upper display: OFF if shunt calibration is disabled, On if shunt calibration is enabled.
Lower display: SHUNT
Range:
OFF, On.
Default value:
On.
SHUNT VALUE - Group 4
Available:
Only if SHUNT parameter is on.
Upper display: Shunt value.
Lower display: SHNT.%
Range:
From 40.0 to 100.0%
Default value:
80.0%
Содержание UPR700
Страница 14: ...14 Fig 2 Model UPR700 Outline Drawing...
Страница 16: ...16 Fig 3 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Primary Input...
Страница 33: ...UPR700 Microprocessor Based Pressure Process Indicator 33 Fig 10 Secondary Input Jumper Location...
Страница 67: ...NOTES...
Страница 68: ...NOTES...
Страница 70: ...DYNISCO LLC 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...
Страница 71: ......