28

In Industrial applications, amplified units have a middle or end number of 4, 5, or 6. The S840-000-
1C has a 4-20 mA signal output; the PT150-7.5M has a 0-5 Vdc signal output, while PT276-5M has
a 0-10 Vdc signal output.

If you have an amplified transducer, or other amplified input, skip to Section 8.4.2.

The UPR700’s default setting is strain gage input. To verify that the input is set for strain gage, press
the 

FUNC

 key until 

nonE

 and 

GROUP

 show on the display. Press the 

 key until 

5

 shows in the

upper display. Press the 

FUNC

 key and the upper display should show 

Str

 while the lower display

shows 

PI.TYP

. If not, press the 

 or 

 key until the upper display changes to 

Str

 (for strain gage).

Press the 

FUNC

 key to set the value. The upper display changes to 

tc

 with 

SI.TYP

 on the lower

display. Press the 

RESET

 key to return to the active display.

Remember to change the jumper settings to correspond to the proper input as shown in Figure 6 for
board location and Figure 7 for amplified input jumpers.

Fig. 6

UPR700 Board Location

Содержание UPR700

Страница 1: ...UPR700 Microprocessor Based Pressure Process Indicator Installation and Operation Manual P N 974090 12 02 Rev F ECO 27358...

Страница 2: ...cifications 7 3 Unpacking 15 4 Dimensional Information 15 5 Hardware 15 6 Mounting and Wiring 18 7 Start Up Procedures 22 8 Configurations 24 9 Operation 42 10 Error Codes 48 11 Normative References 5...

Страница 3: ...move instrument from case by spreading locking tabs Grasp the bezel and slide the instrument out of its case Slide the rubber gasket over the case Slide the instrument case into the cutout Attach the...

Страница 4: ...s 10 000 NOTE If your transducer is a 10 000 psi model skip next two steps Scroll to GROUP Using the Down arrow key set the appropriate Full Scale Value for your transducer Enter using the FUNC key to...

Страница 5: ...y Input Type 8 5 1 32 Set the Secondary Input Scale Value 8 5 2 34 Set the Secondary Input Thermocouple Type 8 5 3 34 Set the Secondary Input Failsafe Mode 8 5 4 34 Alarms Set which input the Alarms w...

Страница 6: ...nsmission output is available as an option as is a 24 VDC power supply for two and four wire process transmitters A third alarm is also available as an option Five groups of configuration parameters a...

Страница 7: ...V AC DC 10 to 10 Power Consumption Max 22 VA at 50 Hz Max 27 VA at 60 Hz Insulation Resistance 100 M 500 VDC Dielectric Strength 2300V rms for 1 min according to EN61010 1 A2 Ambient Temperature From...

Страница 8: ...alarm 3 is in alarm state REM Lit when device is controlled by serial link 0 25 50 75 100 These six LEDs are always on to improve the bar graph indication 2 green LED s annunciator for PEAK Lit when l...

Страница 9: ...y the end user and to restore original factory calibration values Input resolution 400 counts Full scale value Resolution 10 4000 1 digit 4002 8000 2 digits 8005 20000 5 digits 20010 40000 10 digits 4...

Страница 10: ...ed from the primary input A double or reinforced insulation between instrument output and power supply must be guaranteed by the external device 2 6 PRIMARY SECONDARY INPUTS COMMON SPECIFICATION Commo...

Страница 11: ...e Each alarm is keyboard programmable for Primary Secondary input High Low Low inhibited on start up Auto Manual reset Excitation Type Keyboard configurable for each alarm relay coil energized in no a...

Страница 12: ...5 V 0 5 VDC mm load 5 K with under over range capability from 1 25 to 6 25 V 0 20 mA max load 500 with under over range capability from 5 to 25 mA max load 400 over 20 mA 4 20 mA max load 500 with un...

Страница 13: ...ansmission low and high limits are selectable from 0 to primary input full scale value when the retransmitted variable is primary input or from low to high secondary limits when the retransmitted vari...

Страница 14: ...14 Fig 2 Model UPR700 Outline Drawing...

Страница 15: ...mm X 143 5mm Cutout 3 62 X 3 62 92mm X 92mm Depth behind panel 5 04 128mm Weight 1 43 lbs 650g 5 HARDWARE The UPR700 is shipped with the hardware jumpers set for the following Primary Input Pressure S...

Страница 16: ...16 Fig 3 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Primary Input...

Страница 17: ...UPR700 Microprocessor Based Pressure Process Indicator 17 Fig 4 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Secondary Input...

Страница 18: ...fer to the model number of the instrument to determine the hardware and options included as part of your unit Please refer to Section 6 1 for the terminal assignments Terminals are accessed by opening...

Страница 19: ...ast 75 C Use copper conductors only Don t run input wires together with power cables For 24 V DC the polarity need not be observed The power supply input is fuse protected by a sub miniature fuse rate...

Страница 20: ...mA V 23 Remote Reset 24 Remote Reset 45 Alarm 1 NO 46 Alarm 1 Common 47 Alarm 1 NC 48 Alarm 2 NO 49 Alarm 2 Common 50 Alarm 2 NC 51 Alarm 3 Common OPTIONAL 52 Alarm 3 NC NO 53 100 240 VAC OR 24 VAC O...

Страница 21: ...mmon 46 25 A1 N C 47 26 A2 N O 48 27 A2 Common 49 28 A2 N C 50 29 Optional Alarm 3 A3 N O N C 52 21 A3 Common 51 22 Analog Output Voltage Out 21 2 Voltage Out 22 3 Current Out 21 4 Current Out 22 5 Op...

Страница 22: ...0 hysteresis Auto reset failsafe mode and is also linked to the primary input Alarm 3 if supplied is configured as a High Alarm at 80 of the full scale value with 0 4 second filtering 1 0 hysteresis...

Страница 23: ...lay is blank The FUNC function key is used to access the parameter to view and modify The RESET key is used to reset the stored peak value and to reset the alarms when held for 1 second once the alarm...

Страница 24: ...settings for the input s and output s used in your particular application are selected It is necessary only to select the category e g Voltage or Current The specific range will be chosen in the softw...

Страница 25: ...ted for approximately 10 seconds the instrument will automatically return to the normal display mode 8 3 PARAMETER CONFIGURATION PROCEDURES The parameters in the five groups are extensive and not all...

Страница 26: ...er set to OFF the default value of HIGH or to LOW To verify this parameter or to change it press the FUNC key until nonE and GROUP show on the display Press the key until 4 shows in the upper display...

Страница 27: ...t Decimal Point Position PI DP None 1 2 3 4 places None Group 3 Secondary Input T C Type Sl TC tc J tc CA tc L tc n tc J Group 3 Alarm I Input Channel Link AI LNK OFF Prl ln Sec ln Prl ln Group 3 Alar...

Страница 28: ...FUNC key until nonE and GROUP show on the display Press the key until 5 shows in the upper display Press the FUNC key and the upper display should show Str while the lower display shows PI TYP If not...

Страница 29: ...il 4 shows in the upper display Press the FUNC key and the upper display will show OFF while the lower display shows SHUNT Press the or key until the upper display changes to the ON Press the FUNC key...

Страница 30: ...u have a strain gauge transducer load cell or other mV V device see Section 8 4 1 The Instrument s default setting is strain gage input To select another input for a transmitter or to use another proc...

Страница 31: ...ue of 25 of the full scale value To set the low scale value press the FUNC key until nonE and GROUP show on the display Press the key until 3 shows in the upper display Press the FUNC key and the uppe...

Страница 32: ...lues will show in the lower display The Instrument s default secondary input setting is for a J type thermocouple To select another type of input press the FUNC key until nonE and GROUP show on the di...

Страница 33: ...UPR700 Microprocessor Based Pressure Process Indicator 33 Fig 10 Secondary Input Jumper Location...

Страница 34: ...couple type and temperature units by pressing the FUNC key until nonE and GROUP show on the display Press the key until 3 shows in the upper display Press the FUNC key until the lower display shows SI...

Страница 35: ...gh alarm at 60 of full scale linked to the primary input 0 4 second filtering 1 hysteresis automatic reset and failsafe mode The default values for Alarm 3 if supplied are high alarm at 80 of full sca...

Страница 36: ...lied Alarm 3 A3 FL 8 6 4 SETTING THE HYSTERESIS FOR ALARM Hysteresis is used to describe the amount that the reading must drop below the alarm point in a high alarm or must rise above the alarm point...

Страница 37: ...condition or the loss of power to the UPR700 the relay will be de energized and will then close 8 6 7 SETTING THE ALARMS VALUE ALARMS THRESHOLD The Alarm 1Threshold Values is the value beyond which t...

Страница 38: ...ameter or press RESET to return to the operating screen Similarly the Secondary Analog Output Link SO LNK can be set in the same manner 8 7 3 SETTING THE MAIN ANALOG OUTPUT RANGE LOW To change or view...

Страница 39: ...UPR700 Microprocessor Based Pressure Process Indicator 39 Fig 11 Main Analog Output Jumper Location Fig 12 Secondary Analog Output Jumper Location optional...

Страница 40: ...press the FUNC key to lock in the value and advance to the next parameter Similarly the Secondary Analog Output Filter SO FL can be set in the same manner 8 8 SETTING THE SECURITY CODES The security c...

Страница 41: ...he FUNC key to lock in the value The lower display changes to CODE C and the Upper display shows 1 This means that all levels are locked and cannot be changed If finished remove the instrument from it...

Страница 42: ...to ON Press the FUNC key to calibrate the zero value The lower display changes to SPAN C The upper display shows OFF Press the or keys until the upper display changes to ON Press the FUNC key to calib...

Страница 43: ...ss the FUNC key until nonE and GROUP show on the display Press the key until 4 shows in the upper display Press the FUNC key and the upper display should show OFF while the lower display shows SHUNT I...

Страница 44: ...the span value When the legend DSP FL appears in the lower display calibration is complete Press RESET to return to the operating screen 9 2 INSTRUMENT CALIBRATION NOTE In this section the word Calib...

Страница 45: ...vision Zero input counts ZERO Pressure input counts STR Reference junction counts RJ Remote set point linear temperature input and line resistance for RTD input RSP RL Thermocouple and RTD input TC RT...

Страница 46: ...ndary Input Voltage Full scale 10 V S 010 Secondary Input Voltage Verify 2 SL TC Secondary Input Thermocouple Zero 0 mV SH TC Secondary Input Thermocouple Full scale 50 mV S TC Secondary Input Thermoc...

Страница 47: ...E and GROUP show on the display Press the key until 3 shows in the upper display Press the FUNC key and the lower display changes to SC BUS The upper display shows nodbS Press the or keys until the up...

Страница 48: ...re on the transducer and the wiring is correct contact Dynisco Technical Assistance at 800 221 2201 5 Input calibration error Correction Check that there is no pressure applied to the transducer If th...

Страница 49: ...ow OPEN under one or more of the following conditions A D converter saturation indicating a signal outside the expected range Input current lower then 0 8 mA for 4 20 mA inputs Primary input lower the...

Страница 50: ...mounting Nominal front and cut out dimensions EN 61010 1 Safety requirements for electrical equipment for measurements control and laboratory use Part 1 General requirements EN 50081 2 Electromagneti...

Страница 51: ...ilter 8 3 5 A1 FL Alarm 1 Filter 8 6 3 A2 FL Alarm 2 Filter 8 6 3 A3 FL Alarm 3 Filter 8 6 3 MO FL Main Analog Output Filter 8 7 5 SO FL Second Analog Ouput Filter 8 7 5 DEFLT Loading Default Data 8 3...

Страница 52: ...8 6 5 A2 FSM Alarm 2 Failsafe Mode 8 6 6 A3 HYS Alarm 3 Hysteresis 8 6 4 A3 RES Alarm 3 Reset Mode 8 6 5 A3 FSM Alarm 3 Failsafe Mode 8 6 6 LI TYP Logic Input Configuration 8 3 1 LI STS Logic Input S...

Страница 53: ...r with the exception of the selected codes ALARM 1 THRESHOLD Group 1 Available Only if A1 LNK is different than OFF Upper display Alarm 1 threshold value Lower display AL1 Range From low to high scale...

Страница 54: ...FUNC key to start the zero calibration It is also possible to select CLEAr value to delete the field calibration and restore factory calibration Default value Zero SPAN CALIBRATION Group 2 Available...

Страница 55: ...4 5 sec Default value 0 4 sec MAIN ANALOG OUTPUT FILTER Group 2 Available Only if MO TYP is different than OFF Upper display Time constant of the main analog output filter Lower display MO FL Range OF...

Страница 56: ...UT DECIMAL POINT POSITION Group 3 Available Always Upper display Full scale value Lower display PI DP Range Use keys to select the position of the decimal point Default value None SECONDARY INPUT THER...

Страница 57: ...is 0 20 4 20 or 0 10 Upper display Secondary input range high Lower display SI DP Range Use keys to select the position of the decimal point Default value None ALARM 1 INPUT CHANNEL LINK Group 3 Avail...

Страница 58: ...nput Default value Disabled ALARM 3 TYPE Group 3 Available Only if A3 LNK is different than OFF Upper display Selection of alarm 3 type Lower display A3 TYP Range HI LO InhIb High low low with mask at...

Страница 59: ...ilable Only if SO TYP is different than OFF Upper display Range low for second analog output Lower display SO LO Range from 0 to PI FSV if SO LNK PrI In from 1000 to 3000 if SO LNK SEc In Default valu...

Страница 60: ...Default value 19200 LOADING DEFAULT DATA Group 3 Available Only if access to level 3 is allowed Upper display OFF Lower display DEFLT Range Use keys to switch the upper display from OFF to On 3 then p...

Страница 61: ...er display Alarm 1 hysteresis Lower display A1 HYS Range From 0 1 to 10 0 of the selected range Default value 1 0 ALARM 1 RESET MODE Group 4 Available Only if A1 LNK is different than OFF Upper displa...

Страница 62: ...safe mode Default value Failsafe mode ALARM 3 HYSTERESIS Group 4 Available Only if A3 LNK is different than OFF Upper display Alarm 3 hysteresis Lower display A3 HYS Range From 0 1 to 10 0 of the sele...

Страница 63: ...nsidered active when the contact is closed or open with respect to this parameter Default value Closed PEAK DETECTION Group 4 Available Always Upper display Polarity of peak detector Lower display PEA...

Страница 64: ...uple RTD 0 20 mA 4 20 mA 0 10V Default value Thermocouple NOTE Remember to make the proper selection on the hardware jumpers MAIN ANALOG OUTPUT SELECTION Group 5 Available Always Upper display Type of...

Страница 65: ...1 2 3 4 and 5 SECURITY CODE LEVEL A Available Always Upper display 0 1 On Lower display CODE A Range Use keys to input the security codes 0 means no security code all parameters related to level A ar...

Страница 66: ...ocks Level A When the SECUR functions are accessed in Group 1 the levels that are locked will be followed by a decimal point E g A b C indicates that all the levels are locked 13 REPAIR Questions conc...

Страница 67: ...NOTES...

Страница 68: ...NOTES...

Страница 69: ..._________________________ STATE _____________ ZIP __________________ COUNTRY _____________________________________________________________________ TELEPHONE _____________________________ FAX _________...

Страница 70: ...DYNISCO LLC 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...

Страница 71: ......

Страница 72: ...ny sur Marne France Tel 33 1 4881 8459 Fax 33 1 4881 8334 Email DyniscoFrance dynisco com Dynisco s r l Via Adriatico 2 2 20162 Milano Italia Tel 39 02 661 01733 Fax 39 02 661 02908 Email DyniscoItaly...

Отзывы: