UPR700 Microprocessor-Based Pressure/Process Indicator
13
2.12
M
AIN
& S
ECOND
A
NALOG
O
UTPUTS
C
OMMON
S
PECIFICATION
Resolution:
0.1% of output span.
Reference Accuracy:
±
0.1% of output span @ 25
±
10C and nominal line voltage.
Linearity Error:
<0.1% of output span.
Output Noise:
<0.1% of output span.
Scaling:
The retransmission low and high limits are selectable from 0 to primary input full-scale
value (when the retransmitted variable is primary input) or from low to high secondary limits (when
the retransmitted variable is the secondary input). The two scaling values may be freely selectable
within the above range. This allows having a direct or reverse output type.
Output Filter:
Selectable: OFF, 0.4 s, 1 s, 2 s, 3 s, 4 s, 5 s
Fig. 1
Block Diagram of Electronics Layout
NOTE:
Dashed Line represents insulation boundary.