UPR700 Microprocessor-Based Pressure/Process Indicator
61
PRIMARY INPUT FAIL SAFE - Group 4
Available:
Always.
Upper display: Primary input fail safe condition.
Lower display: PI.IFS
Range:
HI, LO.
Default value:
High.
SECONDARY INPUT FAIL SAFE - Group 4
Available:
Only if SI.TYP is different than OFF.
Upper display: Secondary input fail safe condition.
Lower display: SI.IFS
Range:
HI, LO.
Default value:
High.
ALARM 1 HYSTERESIS - Group 4
Available:
Only if A1.LNK is different than OFF.
Upper display: Alarm 1 hysteresis.
Lower display: A1.HYS
Range:
From 0.1 to 10.0% of the selected range.
Default value:
1.0%
ALARM 1 RESET MODE - Group 4
Available:
Only if A1.LNK is different than OFF.
Upper display: Selected reset mode for alarm 1.
Lower display: A1.RES
Range:
Auto, LAtCh. Automatic reset, manual reset.
Default value:
Auto.
ALARM 1 FAILSAFE MODE - Group 4
Available:
Only if A1.LNK is different than OFF.
Upper display: Selected failsafe mode for alarm 1.
Lower display: A1.FSM
Range:
FS, nFS. Failsafe mode, non-failsafe mode.
Default value:
Failsafe mode.
ALARM 2 HYSTERESIS - Group 4
Available:
Only if A2.LNK is different than OFF.
Upper display: Alarm 2 hysteresis.
Lower display: A2.HYS
Содержание UPR700
Страница 14: ...14 Fig 2 Model UPR700 Outline Drawing...
Страница 16: ...16 Fig 3 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Primary Input...
Страница 33: ...UPR700 Microprocessor Based Pressure Process Indicator 33 Fig 10 Secondary Input Jumper Location...
Страница 67: ...NOTES...
Страница 68: ...NOTES...
Страница 70: ...DYNISCO LLC 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...
Страница 71: ......