8
Installation Category:
II
2.3
D
ISPLAY
S
PECIFICATION
Display:
LED technology, custom type.
Upper Digits:
Red color, 5 numeric digits, 7 segments with decimal point 13.2 mm high.
Lower Digits:
Green color, 5 alphanumeric digits (British flag), 14 segments with decimal points.
12.7 mm high.
Bar Graph:
Red color, 35 segment with 3% resolution. Displays continuous bar graph to indicate the
measured variable of the primary input (0-100% full scale). Alarm set point values displayed. Last
segment blinks for pressure greater than full scale value.
Indicators:
9 red LED’s annunciator for:
A1
Lit when alarm 1 is in alarm state
A2
Lit when alarm 2 is in alarm state
A3
Lit when alarm 3 is in alarm state
REM
Lit when device is controlled by serial link
0-25-50-75-100-%
These six LEDs are always on to improve the bar-graph indication.
2 green LED’s annunciator for:
PEAK
Lit when lower display shows the peak value
TEMP
Lit when lower display shows the temperature input value (only for TC and
RTD input)
2.4
P
RIMARY
I
NPUT
S
PECIFICATION
Primary Input:
Selectable between strain gage and linear by jumper and configuration.
Strain Gage Input:
350 Ohm, 2-4 mV/V. Excitation 10 V
±
7%. 6 wire connection.
Input Signal:
-25/125% of full scale (approximately -10 / 50 mV).
Shunt Calibration:
With or without shunt resistor (value programmable from 40.0 to 100.0%).
Zero Balance:
±
25% of full scale (approximately
±
10 mV).
Linear Input:
Selectable between 0-5VDC, 0-10 VDC. 0-20 mA, 4-20 mA.
Auxiliary Power supply:
24 VDC / 1.5W
±
2% power supply for two or four wire transmitter.
Содержание UPR700
Страница 14: ...14 Fig 2 Model UPR700 Outline Drawing...
Страница 16: ...16 Fig 3 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Primary Input...
Страница 33: ...UPR700 Microprocessor Based Pressure Process Indicator 33 Fig 10 Secondary Input Jumper Location...
Страница 67: ...NOTES...
Страница 68: ...NOTES...
Страница 70: ...DYNISCO LLC 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...
Страница 71: ......