Control Wiring Requirements
Motor Controller and Ground Wiring Specifications
Use approved wire meeting local electrical code requirements between the Motor Speed Control
Interface and the motor speed controller. 16-gauge wire is sufficient for all ground wires.
Multi-Cable Specifications
One multi-cable with the following specifications is required between each sensor and the DM510
Control Panel. See below for details.
•
Two-pair shielded, minimum 22 AWG (.644 mm or 23 SWG) stranded tinned copper
conductors and drain wire (e.g. Beldon #8723).
•
PVC jacket rated for 140°F (60°C). The Dryer Master supplied wire is rated to 105°C.
•
Colour code: black, red, green, white (recommended).
•
In areas where the temperature will exceed 140°F, use a wire with a higher jacket
rating (e.g. Beldon #88723).
Figure 25
–
Multi-Cable Diagram
Note:
All electrical installations must meet local electrical code requirements
Caution
All multi-cable must be run in areas where the maximum temperature does not exceed 105°C
(220°F). Use Teflon coated wires in areas that exceed this limit.