Typical System Multi-Cable Requirements
See Figure 26 - Wire placement for a list of the multi-cable requirements and wire placement for a
DM510 system with ALL options. To accommodate this number of cables (10 cables at .170” or
4.318 mm diameter) a ¾ “, 19.05mm conduit is required. There are two cable entry locations at the
bottom right h
and side of the cabinet sized for a ¾ “, 19.05mm conduit
for ease of installation. See
Figure 27 - Wire Entry Locations
Number
Quantity
From
To
1
1 Multi-Cable + 1 ground
Inlet Moisture Sensor
DM510 Control Panel
2
1 Multi-Cable + 1 ground
Outlet Moisture Sensor
DM510 Control Panel
3
1 Multi-Cable
Remote Calibration Button
DM510 Control Panel
4
2 Multi-Cables
Drying Air Temperature
Sensor
DM510 Control Panel
5 and 6
2 Multi- 1
ground
Motor Speed Control
Interface and Local/Remote
Status
DM510 Control Panel
7
1 Multi-Cable
Fan Status (optional)
DM510 Control Panel
8
1 Multi-Cable
Spare
DM510 Control Panel
9
1 Multi-Cable
Remote alarm (optional)
DM510 Control Panel
10 and
11
2 Multi-Cable
I/O Panel
DM510 Control Panel
1 If your system came with a supplied drying air temperature sensor (Figure 29 - Air Plenum Temperature Sensor) install it
near the existing temperature sensor and use High Temperature Teflon coated wire where necessary. If your systems came
with a signal converter (Figure 30 - Temperature Signal Converter) install the signal converter as per the instructions in
Appendix 2.
Figure 26 - Wire placement
Figure 27 - Wire Entry Locations