Page | 39
Dryer Master DM510
Installation Manual
Power and Grounding Requirements
DM510 Control Panel
Power
The DM510 can be powered with 85 to 264 VAC, 47 to 440 Hz or 120 to 370 VDC. The Dryer Master
requires less than 175 watts that should be provided with a dedicated, isolated grounded circuit.
Grounding AC Power
The DM510 must be provided with a good earth ground. It is recommended that a UPS
(Uninterruptible Power Supply) be used for best surge and lightning protection. An isolated ground
connected directly into the control panel will assure the equipment is grounded even if it is
unplugged.
Damage caused by electrical surges and lightning are not warranted.
System Grounding Configuration
A typical electrical installation includes a number of electrical devices or equipment each with its
own ground connection. The relationship between these ground connections will affect the overall
performance of the system especially during a transient event such as lightning strikes.
Important:
All electrical installations must meet local electrical code requirements.
Note:
Although the information in this section is provided in an attempt to reduce damage to the Dryer
Master due to lightning strikes, it will not necessarily eliminate all lightning damage.