Page | 48
Dryer Master DM510
Installation Manual
Wiring Instructions (Cable Terminations)
Tools Required
You will need the following tools to prepare and terminate the Multi-Cable:
•
Wire Strippers
•
Cable Strippers
•
Side Cutters
•
Small needle nose pliers
•
Crimping tool for insulated connectors
•
Small screwdriver 1/8" (3mm)
General Wiring Procedure
The following steps demonstrate how to prepare the Multi-Cable without causing damage to the
individual conductors.
1.
At the DM510 Control Panel end, cut all Multi-Cables so that each will reach 3" (7 cm) past
the furthest connector on the interface board making sure that all the wire numbers are
placed such that they will be visible for reference.
2.
Use the wire strippers to remove ½" of the PVC outer jacket and expose the ripcord (if the
cable is so equipped). Use the needle nose pliers to pull ripcord so the desired length of wire
is exposed. Cut off the original ½" of the cable as it may have been nicked when the PVC
jacket was removed and could cause problems at a later date.
3.
Remove the insulation using cable strippers. The use of a knife is not recommended because
of the risk of damaging the insulation of the conductors.
4.
Use the side cutters to trim the jacket, ripcord and foil shield.
DO NOT CUT OFF THE DRAIN
WIRE
at the DM510 Control Panel end. Use the side cutters to cut the rest of the wires to a
uniform length.
5.
When all wiring has been completed, join all the drain wires together at the DM510 Control
Panel end. The shields should be connected to the grounding pigtail provided in the vertical
cable tray located beside the I/O board within the DM510 cabinet. Only one end of the shield
wire is to be connected to ground. Connect all these wires to the ground wire provided by
the DM510 Control Panel.