27
F_06
: frequency upper limit
range=00.0-01.0~200Hz
F_07
: frequency lower limit
range=00.0-01.0~200Hz
F_06 :Factory setting refer to F_25.
NOTE:
a: If F_07 = 0 Hz, The frequency instruction is equal to 0Hz, the inverter will
stop at 0 speed and display
OSP
b: If F_07 > 1 Hz, The frequency instruction F_07, the inverter will
Output a minimum speed according to the setting in F_07
F_08
: SP1 frequency range: 00.0-01.0 ~ 200Hz
F_08 SP1 is active when forward or reverse command is given without SP2 or SP3 command.
The priority of reading frequency setting is :
1.
Preset speeds
2.
Keypad setting
3.
External frequency signal using a speed pot
F_09
: Current limit stall level during acceleration or at constant speed.
Range: 000-020~150 sets level of current limit protection within inverter
Setting 000= current limit is disabled.
Setting 020~150% inverter will try to keep operating current within this level.
F_10
: Start / Stop Control
= 000 : Keypad
= 001 : Terminal (TM2) low voltage or D61538 (120V) / D61539 (24V) (TB1)
NOTE: When F_10=1 (Terminal Control), emergency stop on the Keypad is enabled.
When operating the inverter from the keypad, inverter speed is commanded by
pressing the up and down arrows on the keypad. Direction is commanded by
F_04.