: Multifunctional input terminal 1 function range: 001~ 006
F_20
: Multifunctional input terminal 2 function range: 001~006
1.
F_19=001 , F_20 =001
Multi-speed control:
TB1 - #5 Terminal
TB1 - #6 Terminal
Output frequency
O N
O FF
F_2 6
O FF
O N
0-
Ser
O N
O N
F_2 7
2.
F_19, F_20=002: External emergency stop. N/C contact for running.
When the external emergency stop signal is activated, the inverter activates coast to stop,
(ignoring the setting of F_14). The inverters display light will flash
ES
after stopping. After the
emergency stop signal is deactivated, turn the RUN switch O FF and then O N again to cycle it.
(F_10=1) O r, push the RUN key (F_10=0). The inverter will then resume operation and
restart. If the emergency stop signal is removed before the inverter stops, the inverter will still
execute the emergency stop.
3.
F_19, F_20=003: External Base Block (Immediate Shut Down) N/O contact for
running.
When the external base block signal is activated, the inverter output will be immediately shut
off (ignoring the setting of F_14) and flash
b.b.
light. After the base block signal is deacti-
vated, the inverter will restart from the original starting frequency without the free-run stop time
delay.