burner with pneumatic linkage
dreizler A 3001 E - 18.12.2015 | A 2003 - 1.10 | EN - 11.11.2010
29
Air pressure at the burner head should not be set below 1mbar at MIN load. Adjust this point at switch-
ing cam MIN of the servomotor.
Fig. 9-7 Adjusting the servomotor
1
MIN adjustment only via servomotor (>1mbar)