![Dreizler marathon M 10001.1 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/dreizler/marathon-m-10001-1/marathon-m-10001-1_manual_2530578061.webp)
Servomotor type SQM 5...
dreizler A 3001 E - 18.12.2015 | A 2027 - 2.14 | EN - 11.11.2014
61
18.2 Preadjustment of the servomotor SQM 5...
The following drawings show the allocation of the switching cams of servomotor SQM 5... on the example
SQM 54 anti-clockwise rotation model in delivery condition ex works.
Tab. 18-1 Example: Setting the switching cams for SQM 54... anti-clockwise rotation
Switching position cam I at MAX (full load)
Limit switch switches at MAX load 90° between 1
and 11 to throughput.
Switching position cam II, zero position of air damper
Limit switch switches at switching point approx. 0°
between 2 and 22 to throughput.
Switching position cam II at ignition load
Limit switch switches at ignition load at 40°
between 3 and 23 to throughput.
Switching position cam IV at MIN (small load)
Limit switch switches at MIN load approx. 30°
between 4 and 24 to throughput.
Содержание marathon M 10001.1
Страница 14: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 14...
Страница 15: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 15...
Страница 16: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 16...
Страница 56: ...Servomotor Type SQN 7 dreizler A 3001 E 18 12 2015 A 2025 2 14 EN 11 11 2014 56...
Страница 166: ...Basic calculations dreizler A 3001 E 18 12 2015 A 2048 1 12 EN 09 11 2012 166...
Страница 171: ...Maintenance dreizler A 3001 E 18 12 2015 A 2044 1 15 EN 18 05 2015 171 Fig 53 1 Tightening torque of threaded plugs...