46.2.3 Setpoint limits
Configuring the upper and lower setpoint limits:
NOTICE:
The controller regulates its setpoints precisely.
Example 1:
Lower setpoint limit 50°C
Setpoint low
- Hysteresis 1
= lower setpoint limit
SPL
- HYS1
= lower setpoint limit
53 digits
- 3 digits
= 50 digits
Example 2:
Upper setpoint limit 90°C
Setpoint high
- Hyteresis 3
= upper setpoint limit
SPH
- HYS3
= upper setpoint limit
85 digits
- 5 digits
= 90 digits