Air pressure switch
dreizler A 3001 E - 18.12.2015 | A 2029 - 2.14 | EN - 11.11.2014
131
40.2 Configuring the air pressure switch
dreizler
®
gas power burners are equipped with air pressure switches as standard, which are set to the pres-
sure range of the burner as differential pressure on the blower.
NOTICE:
These air pressure switches must be set to 80% of min. differential pressure (in accordance with DIN/EN
676 'Gas power burners').
NOTICE:
An unalterable trouble shut-off occurs if the air pressure value falls below the preset value.
The burner must then be manually unlocked by pressing the release button on the automatic gas control
box.
The air pressure switch must be set by a technician during commissioning and must be checked during
each maintenance. The standard value is the air pressure value during pre-purge phase, and not the air
pressure value during burner operation.
Measuring the min. differential pressure by way of a differential pressure manometer during pre-purging
Configuring the air pressure switch to 80% of min. value.
40.3 marathon
®
gas burner model with air pressure switch
40.3.1 marathon
®
burner - standard version
Burner sizeStandard
version
Air pressure switch
Configuration range
Air pressure switch
type
Factory configuration
Dungs
121
0.5 - 5 mbar
LGW 10 A2
2.8 mbar
201
1.0 - 10 mbar
LGW 10 A2
5.5 mbar
301
2.5 - 50 mbar
LGW 50 A2
11 mbar
601
2.5 - 50 mbar
LGW 50 A2
15 mbar
1001
2.5 - 50 mbar
LGW 50 A2
14 mbar
1501
2.5 - 50 mbar
LGW 50 A2
21 mbar
2001
2.5 - 50 mbar
LGW 50 A2
21 mbar
3001
2.5 - 50 mbar
LGW 50 A2
21 mbar
5001.1
2.5 - 50 mbar
LGW 50 A2
23 mbar
5001
2.5 - 50 mbar
LGW 50 A4
28 mbar
10001
2.5 - 50 mbar
LGW 50 A4
depending on
system conditions
10003
2.5 - 50 mbar
LGW 50 A4
depending on
system conditions
Содержание marathon M 10001.1
Страница 14: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 14...
Страница 15: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 15...
Страница 16: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 16...
Страница 56: ...Servomotor Type SQN 7 dreizler A 3001 E 18 12 2015 A 2025 2 14 EN 11 11 2014 56...
Страница 166: ...Basic calculations dreizler A 3001 E 18 12 2015 A 2048 1 12 EN 09 11 2012 166...
Страница 171: ...Maintenance dreizler A 3001 E 18 12 2015 A 2044 1 15 EN 18 05 2015 171 Fig 53 1 Tightening torque of threaded plugs...