Ignition transformer
dreizler A 3001 E - 18.12.2015 | A 2042 - 1.09 | EN - 23.10.2009
75
22.2 Ignition transformer ZM 20 / 10 (2-pole)
22.2.1 Description
The 2-pole ignition transformer is earthed at the centre point of the secondary development. The transform-
er ignites electrode against electrode; ignition from one electrode to mass must not occur. The 2-pole igni-
tion transformer generates less radio interference levels.
22.2.2 Technical data
NOTICE:
The best spark gap distance is between 2 and 3mm.
22.2.3 2-pole ignition:
Fig. 22-2 Electrode gap in 2-pole ignition
22.3 Ignition transformer configuration
22.3.1 Gas burner
Secondary voltage:
2 x 5kV
Short-circuit current:
20mA (60Hz 15mA)
Power input voltage:
230V / 50Hz
Rated input voltage:
1.1A (60Hz 0.8A)
Intermittent operation:
AB 33% (3 minute duty cycle)
Burner model size
Ignition transformer
M 121 - M 1501:
Burner management system ORBIC with integrated high-frequency
transformer
M 2001 - M 5001:
Burner management system ORBIC with ZM 20 / 10 ignition trans-
former
M 5001.4, M 10001 - M 10003:
Burner management system ORBIC with 2 x ZE 30 / 7.5 ignition
transformer
Содержание marathon M 10001.1
Страница 14: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 14...
Страница 15: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 15...
Страница 16: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 16...
Страница 56: ...Servomotor Type SQN 7 dreizler A 3001 E 18 12 2015 A 2025 2 14 EN 11 11 2014 56...
Страница 166: ...Basic calculations dreizler A 3001 E 18 12 2015 A 2048 1 12 EN 09 11 2012 166...
Страница 171: ...Maintenance dreizler A 3001 E 18 12 2015 A 2044 1 15 EN 18 05 2015 171 Fig 53 1 Tightening torque of threaded plugs...