Connection parts for marathon
®
gas burners with pneumatic linkage
dreizler A 3001 E - 18.12.2015 | A 2053 - 1.15 | EN - 18.05.2015
98
30.3 Connection parts betw. burner head and gas ramp with gas controls VGD and SKP
75
NOTICE:
Verify correct control line connections during installation (see pos. 10+11)!
The correct position of the air impulse tap P (9) at the swirl plate is in flow direction, see Fig. 30-5 "Connec-
tion parts VGD + SKP"
- the burner sizes M 121 up to M 3001 on 10:00 - 11:00 o’clock position
- the burner sizes M 5001.1, M 5001 and M 5001.4 on 3:00 o’clock position
Other positions may cause a nonlinear control behaviour of the pneumatic gas/air linkage (nonlinear
adjustment of the oxygen content in the exhaust gas)!
Fig. 30-6 Example for position P
air
for M 121 up to M 3001
Fig. 30-5 Connection parts VGD + SKP
1 burner head
2 flame tube
3 burner housing
4 Schott push-on connector
5 Schott push-on connector
6 hose
7 hose
8 pipe
9 pipe
10 hose
P
f
combustion chamber pressure
black
11 hose
P
L
air blue
12 VGD + SKP 75
13 quick coupling piece
14 gas ramp
15 plug nipple
16 swivel plate
Содержание marathon M 10001.1
Страница 14: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 14...
Страница 15: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 15...
Страница 16: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 16...
Страница 56: ...Servomotor Type SQN 7 dreizler A 3001 E 18 12 2015 A 2025 2 14 EN 11 11 2014 56...
Страница 166: ...Basic calculations dreizler A 3001 E 18 12 2015 A 2048 1 12 EN 09 11 2012 166...
Страница 171: ...Maintenance dreizler A 3001 E 18 12 2015 A 2044 1 15 EN 18 05 2015 171 Fig 53 1 Tightening torque of threaded plugs...