Settings for burner with electronic linkage
dreizler A 3001 E - 18.12.2015 | A 2041 - 3.14 | EN - 11.11.2014
33
11.3 Procedure
11.3.1 Setting the end stops
The end stops of the actuators are adjusted at the relevant limit switches of the servomotors.
Configure the limit switches as follows:
11.4 Settings for the potentiometer
The conductive potentiometer (electronic) with its feedback function is set in a range of between 180 - 900
digits so that it can send messages independent of position.
CAUTION!
Pay attention to the assembly and placement of the potentiometer (torque slotted screw).
11.5 Configuring the frequency converter
Configuring the frequency converter and allocation of position-independent frequencies:
The frequency converter is assigned a particular motor speed and load position value as described in chap-
ter 45 "Frequency converter 'frequency'".
Fixed values are:
11.6 Configuration of the burner management system ETAMATIC OEM
A detailed operating manual for ETAMATIC OEM is included in the appendix. Please read the operations
manual carefully before commissioning the system.
NOTICE:
Due to the programmed linkage control curves, the Etamatic OEM may only be used for the burner installed
with it. An application of the Etamatic for other or structurally identical burners is only possible by resetting
to this burner or by qualified engineers.
11.7 Configuring the load point
Set the required gas supply pressure at the gas pressure switch (SKP25 or MBC).
Check the ignition point.
Set the remaining operating points at the relevant controllers in the system accordance with the oper-
ating instructions for ETAMATIC OEM.
Proceed to store the data as 'Protected record'.
Gas damper min. to max.
=
0-90°
Air damper min. to max.
=
0-90°
Oil regulator min. to max.
=
0-135° (0-90° in the type BT 3xx)
MAX load
Motor speed
Frequency
100%
3000 min-1
50 Hz
20%
1000 min-1
20 Hz
Содержание marathon M 10001.1
Страница 14: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 14...
Страница 15: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 15...
Страница 16: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 16...
Страница 56: ...Servomotor Type SQN 7 dreizler A 3001 E 18 12 2015 A 2025 2 14 EN 11 11 2014 56...
Страница 166: ...Basic calculations dreizler A 3001 E 18 12 2015 A 2048 1 12 EN 09 11 2012 166...
Страница 171: ...Maintenance dreizler A 3001 E 18 12 2015 A 2044 1 15 EN 18 05 2015 171 Fig 53 1 Tightening torque of threaded plugs...