Gas high-pressure overload protection (Gas pressure switch MAX)
dreizler A 3001 E - 18.12.2015 | A 2031 - 1.09 | EN - 23.10.2009
127
39 Gas high-pressure overload protection
(Gas pressure switch MAX)
A device that compares the current pressure value with the desired value and provides a signal if the cur-
rent value surpasses a set value. Once the set value is surpassed, an unalterable trouble shut-off occurs.
NOTICE:
In accordance with EN 676, the installation of a gas high-pressure overload protection in steam boilers and
powered pressure devices is mandatory in order to prevent an overload of the powered pressure device.
NOTICE:
For more information about type-specific component characteristics, please see relevant manufacturer
documentation.
39.1 Function of gas pressure switch MAX
Gas pressure switch MAX
The differential gap is
1.0mbar and max. load overpressure is
600mbar.
Fig. 39-1 Gas pressure switch MAX
Fig. 39-2 Layout of gas pressure switch MAX
2 - 3 Circuit closes with increasing
NO COM pressure
1 - 3 Circuit closes with decreasing
NC COM pressure
Содержание marathon M 10001.1
Страница 14: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 14...
Страница 15: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 15...
Страница 16: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 16...
Страница 56: ...Servomotor Type SQN 7 dreizler A 3001 E 18 12 2015 A 2025 2 14 EN 11 11 2014 56...
Страница 166: ...Basic calculations dreizler A 3001 E 18 12 2015 A 2048 1 12 EN 09 11 2012 166...
Страница 171: ...Maintenance dreizler A 3001 E 18 12 2015 A 2044 1 15 EN 18 05 2015 171 Fig 53 1 Tightening torque of threaded plugs...