Gas low pressure protection (Gas pressure switch MIN)
dreizler A 3001 E - 18.12.2015 | A 2030 - 1.09 | EN - 23.10.2009
125
38.2 Configuring the gas pressure switch MIN
NOTICE:
If nominal supply pressure falls below 75%, the gas pressure switch MIN turns the burner off. Once pres-
sure rises again, the gas burner restarts automatically.
Configuration process:
1) Gas burner runs at nominal supply pressure in position QB MAX.
2) Supply pressure is decreased to 75% via the ball valve.
3) The gas pressure switch MIN must switch off at that supply pressure. Adjust accordingly.
38.3 Installation type gas pressure switch MIN
The gas pressure switch MIN is located upstream of the gas pressure switch. The position of the gas pres-
sure switch MIN is defined in the gas ramp diagram.
Nominal connection
pressure (mbar)
upstream of gas
ramp
Configuration pres-
sure
(mbar)
gas pressure switch
Max. configuration
range (mbar)
gas pressure switch
Gas pressure
switch Krom-
schröder
Gas pres-
sure switch
Dungs
20
15
50
1
DG50B
1. In CG dual fuel mountings, internal gas pressure switch
2
GW50A5
2. Alternative: GW...A6 in specialist constructions.
50
40
50
100
80
150
DG150B
GW150A5
250
180
500
DG 500B
GW500A5
Содержание marathon M 10001.1
Страница 14: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 14...
Страница 15: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 15...
Страница 16: ...CE certification and declaration of conformity dreizler A 3001 E 18 12 2015 A 2001 1 13 EN 17 06 2013 16...
Страница 56: ...Servomotor Type SQN 7 dreizler A 3001 E 18 12 2015 A 2025 2 14 EN 11 11 2014 56...
Страница 166: ...Basic calculations dreizler A 3001 E 18 12 2015 A 2048 1 12 EN 09 11 2012 166...
Страница 171: ...Maintenance dreizler A 3001 E 18 12 2015 A 2044 1 15 EN 18 05 2015 171 Fig 53 1 Tightening torque of threaded plugs...