Page 83 of 145
Power
Petro-Net
Module Board
Power Supply
12.3
SiteSentinel® iSite™ Smart Module
The Smart Module gathers probe and sensor data. Up to four devices
can be connected to the Intrinsically Safe (I.S.) barrier in the Smart
Module. The barrier isolates the module from hazardous areas where
probes and sensors are installed. Up to four (4) barriers can be in
each module, a total of 16 devices per module. Up to eight modules
can be connected to the console via Petro-
Net™ (twisted-pair) wiring,
for a total of 128 devices per system. Conduit is recommended for the
Petro-
Net™ wiring between the Smart Module and the console, but it
is
not
required.
The standard Smart Module includes one I.S. barrier. The part
number for additional I.S. barriers is 20-4343.
Figure 12-
3 SiteSentinel® iSite™ Smart Module Connections
Smart Module Specifications
Electrical Requirements
Standard Voltage Supply:
Optional Voltage Supply:
Power Consumption:
105 to 125 VAC, 60 Hz
220 to 240 VAC, 50 Hz
60 W maximum
Dimensions
Width:
Height:
Depth:
17” (43.2 cm)
9.75” (24.8 cm); Mounting Tabs add 1”
(2.5 cm) top and bottom
5.5” (14 cm); Key adds 1.5” (3.8 cm)
Mounting Centers:
16.5” (41.9 cm) width by 11” (27.9 cm)
height
Temperature Range:
32
F to 104
F (0
C to 40
C)
Device Capacity
per I.S. Barrier:
per Smart Module:
per System:
up to four (4) devices
up to 16 devices
up to 128 devices
Probe Cable Requirement:
Belden #88760 or Alpha #55371 cable
(shielded two-wire twisted pair)
Sensor Wiring Requirement:
14- to 18-AWG oil-and-gas resistant
(TFFN, THHN or THWN)
Petro-
Net™ Communication
Wiring Requirement:
18-AWG, twisted pair, oil-and-gas
resistant (TFFN, THHN or THWN)
Maximum Petro-
Net™
Extension:
5,000’ (1.5 km)
Содержание OPW SiteSentinel iSite
Страница 15: ...Page 15 of 145 www opwglobal com Figure 2 4 Console Connectivity ...
Страница 17: ...Page 17 of 145 www opwglobal com Figure 2 6 Wiring Connections ...
Страница 22: ...Page 22 of 145 www opwglobal com Figure 2 11 Standard Twisted Pair Petro Net Installation ...
Страница 25: ...Page 25 of 145 www opwglobal com Figure 2 14 Petro Net Over Ethernet Option ...
Страница 33: ...Page 33 of 145 www opwglobal com ...
Страница 34: ...Page 34 of 145 www opwglobal com Figure 4 1 924B Probe Installation ...
Страница 61: ...Page 61 of 145 www opwglobal com Figure 5 22 In Tank Probe Setup ...
Страница 74: ...Page 74 of 145 www opwglobal com Figure 9 3 Dry Well Monitoring Single Wall Tank ...
Страница 78: ...Page 78 of 145 www opwglobal com Figure 9 7 Double Wall Tank with Well Monitoring ...
Страница 90: ...Page 90 of 145 www opwglobal com Figure 13 7 ACR RIM Jumper Board ...
Страница 142: ...Page 142 of 145 www opwglobal com Declaration of Conformity ...
Страница 143: ...Page 143 of 145 www opwglobal com ...
Страница 146: ...Page 146 of 145 www opwglobal com NOTES ...