8
BH 5911 / 151007 / 478
Technical Data
General Data
Operatinng mode:
Continuous
Temperature range:
±
0 ... + 50 °C
At an operating temperature of 50 °C
the modules must be mounted with
a distance of 3 - 5 mm.
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
4 kV / 2 (basis insulation) IEC 60 664-1
EMC:
IEC/EN 61 326-3-1, IEC/EN 62 061
Radio interference
suppression:
Limit value class A
EN 55 011
Remark: This device is designed for industrial ambient conditions.
When used in other environment, it is possible that wire bound or
radiated interference occurs.
Degree of protection
Housing:
IP 20
IEC/EN 60 529
Terminals:
IP 20
IEC/EN 60 529
Housing:
Thermoplast with V0 behavior
according to UL Subject 94
Vibration resistance:
Amplitude 0.35 mm
Frequency 10 ... 55 Hz, IEC/EN 60 068-2-6
Shock resistance:
Acceleration:
10 g
Pulse duration:
16 ms
Number of shocks:
1000 per axis on three axes
Climate resistance:
0 / 050 / 04
IEC/EN 60 068-1
Terminal designation:
EN 50 005
Wire connections:
DIN 46 228-1/-2/-3/-4
Wire fixing:
Plus-minus terminal screws M3,5
box terminals with wire protection
Surge supression:
When connecting inductive loads to the
relay outputs (contactor coils, valves,
electric brakes) surge supressor elements
like diods, capacitros, RC combinations,
etc. have to be connected directly to the
connection terminals of the controlled
devices, keeping the connection wires
as short as possible.
Mounting:
DIN rail
IEC/EN 60 715
Dimensions
Width x height x depth:
45 x 84 x 121 mm
Ordering Example
BH 5911.03/00MF0 DC24V
3 NO contacts
BH 5911.22/00MF0 DC24V
2 NO contacts, 1 NC contact
CSA-Data
Wire connection:
60°C / 75°C copper conductors only
AWG 20 - 12 Sol Torque 0.8 Nm
AWG 20 - 14 Str Torque 0.8 Nm
nfo
Technical data that is not stated in the CSA-Data, can be found
in the technical data section.
CCC-Data
Thermal current I
th
:
4 A
Switching capacity
to AC 15:
3 A / AC 230 V
IEC/EN 60 947-5-1
to DC 13:
1 A / DC 24 V
IEC/EN 60 947-5-1
nfo
Technical data that is not stated in the CCC-Data, can be found
in the technical data section.