1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
92/105
41.33
B
1PH -
B
2PH: P
UMP
D
OWN STOP ALARM FROM PRESSURE SWITCH
/ L
OW PRESSURE
SWITCH
Label on the display
b1PH
(Pump down stop alarm of the circuit 1)
b2PH
(Pump down stop alarm of the circuit 2)
Origin
Pressure switch: if CO36 = 1,2,3,4 and ID not active, the pump down stops because of the timeout
CO39.
Transducer: if CO36 = 1,2,3,4 and the set CO37 is not reached: the pump stops because of the
timeout CO39.
Reset
From thermoregulation start-up and ID not active
From thermoregulation start-up with evaporating pressure higher than CO37 + CO38 (differential)
Restart
Automatic – Manual and logged after AL21 events per hour (reset procedure in function menu).
Icon
Blinking
Action
Alarm relay + buzzer ON when it becomes manual
41.34
B
1PL -
B
2PL A
LARM DURING THE
P
UMP
D
OWN START
-
UP FROM PUMP DOWN PRESSURE
SWITCH
/ L
OW PRESSURE TRANSDUCER
Label o the display
b1PL
(pump down alarm in start-up of circuit #1)
b2PL
(pump down alarm in start-up of circuit #2)
Origin
Pump down pressure switch : CO36 = 1,2,3,4 and compressors start-up and digital input not active
for the time set in CO39
Pump down transducer: CO36 = 1,2,3,4, compressors start-up and the set CO37 is not reached in
the interval time CO39.
Reset
From thermoregulation start-up and ID not active
From thermoregulation start-up with evaporating pressure higher than CO37 + CO38 (differential)
Restart
Automatic - Manual and logged after AL21 events per hour if AL23=1 (reset procedure in function
menu).
If AL23 = 0 it is automatic and not logged.
Icon
Blinking
Action
Alarm relay + buzzer ON when it becomes manual
41.35 C1M
N
- C2M
N
- C3M
N
- C4M
N
- C5M
N
- C6M
N
C
OMPRESSOR MAINTENANCE
Label o the display
C1Mn
(Compressor #1 maintenance) –…
C6Mn
(Compressor #6 maintenance
)
Origin
Compressor running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Icon
Blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
41.36 AEP1 - AEP2 P
UMP
/
SUPPLY FAN MAINTENANCE
Label o the display
AEP1
(Evaporator #1 pump maintenance)
AEP2
(Evaporator #2 pump maintenance)
Origin
Pump/supply fan running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Icon
Blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...