1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
20/105
7.6 A
NALOG
I
NPUT FOR
P
RESSURE
R
ATIOMETRIC
T
RANSDUCER
P
PR
30 (0 ÷ 5V
SIGNAL
)
Using 5V ratio-metric pressure transducer set the Parameter CF07 = 2 / 3
7.7 PWM
O
UTPUT FOR
C
ONDENSING
F
AN
S
PEED
C
ONTROL
With only one condensing circuit configured the TF1 / TF2 outputs work together. The PWM signal can control the cut phase controllers
for the following mono-phase models:
Mod. XV05PK mono-phase , cut phase control 500 Watt (2A)
Mod. XV10PK mono-phase , cut phase control 1000 Watt (4A)
Mod. XV22PK mono-phase , cut phase control 2200 Watt (9A)