Note: During the defrost and when the compressor is off in dripping time the pump is on.
33.3
H
OT
S
TART
FA25
Hot start Setpoint
Low temperature value of PB2 to stop the supply fan.
This function is available
only
with air / air unit configured as
heat pump
and allows to run the supply fan only when the air temperature
is enough hot.
FA26
Hot start differential
Temperature differential of the hot start function.
34 WATER PUMP OF THE CONDENSER
34.1 C
ONDENSER
W
ATER PUMP CONTROL
If one relay is configured as condenser water pump the
CO24 / CO25
parameter values do not affect the pump functioning..
Water pump regulation:
Operative mode of the condenser water pump parameter CO21
CO21 = 0
Not enabled, pump not controlled.
CO21 = 1
Continuous control. The water pump is running only if the unit is running (chiller, heat pump). After giving the the start in
chiller or heat pump mode the compressor regulation starts only after the time delay CO17.
The water pump is turned off only when the unit is turned off (stand-by) and, if CO23<>0, the water pump/ supply fan turns off only after
the this delay.
When the unit is in stand-by or remote off and the Ar09 =1, if the thermoregulation requires the antifreeze heaters also the water pump
is turned on.
CO21
= 2
on compressor demand.
When the compressor turns on also the water pump is turned on. In both chiller and heat pump modes the water pump/ supply fan
starts CO17 before the compressor. When the last compressor is turned off the water pump/ supply fan is turned of after the CO23
delay.
When the unit is in stand-by or remote off and the Ar09 =1, if the thermoregulation requires the antifreeze heaters also the water pump
is turned on.
The pump is always off when:
•
Remote OFF from digital input.
•
Digital input active of the condenser water pump overload.
•
Digital input active of the condenser water pump flow with MANUAL alarm.
During the defrost and when the compressor is off in dripping time the pump fan is on.
35 PUMP GROUP OF THE CONDENSER
If two relay outputs are configured as condenser water pump and support pump of the condenser automatically the pump group control
is enabled.
First start-up of the unit: the running hours of the two pumps are both 0, if CO21=1 or 2 (continuous or on compressor demand pump
mode) by default the pump #1 is turned on. The successive restart of the unit is made with the pump #2.
During the normal functioning condition when the unit changes from a stand-by /remote off/ power off status to chiller or heat pump
mode the pump that is running is switched off and immediately the one with less running hours is turned on.
When the unit goes in stand-by or remote off the pump stays on for the time set in CO23.
When the unit is in stand-by or remote off and the Ar09 =1, if the thermoregulation requires the antifreeze heaters also the water pump
is turned on.
35.1 C
ONDENSER WATER PUMP ROTATION
Par.
CO24
<> 0 to enable the function.
During the normal functioning condition, both for chiller and heat pump, if one pump reaches the running hours of the CO24 parameter,
the pump is turned off while the other pump is re-activated.
If the CO25 <> 0, before changing from one to the other the two pumps work together for the time set in this parameter. If CO24=0 the
rotation is immediate and CO25 is not counted.
ATTENTION
The CO17/CO23 values, on and off delay between compressors and pumps, are calculated also for the pump group.
35.2 C
ONDENSER
W
ATER
P
UMP ROTATION THROUGH DIGITAL INPUT CONTROL
With two digital inputs configured as overload alarm of water pump and support pump the rotation is enabled when the digital input of
the running pump becomes active. That pump is turned off while the other is forced on.
If only one digital input is configured as condenser water pump alarm or only as condenser water pump alarm the active digital input
alarm stops the corresponding pump.
During the defrost and when the compressor is off in dripping time the pump is on.
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...