1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
dF 11
Temperature setpoint for combined defrost end of the 1
st
circuit. -30.0
-22
70.0
158
°C
°F
Dec
int
dF 12
Temperature setpoint for combined defrost of the 2
nd
circuit after parameter
DF10 counting.
-30.0
-22
70.0
158
°C
°F
Dec
int
dF 13
Temperature setpoint for combined defrost end of the 2
nd
circuit. -30.0
-22
70.0
158
°C
°F
Dec
int
dF 14
Activation of all the steps of the 1
st
circuit during the defrost.
0= Not enabled
1= Enabled
0 1
dF 15
Activation of all the steps of the 2
nd
circuit during the defrost.
0= Not enabled
1= Enabled
0 1
dF 16
Time delay between two compressor ON in defrost mode
0
250
Sec
dF 17
Fan control during defrost / dripping time
0= Not enabled
1= Only in defrost
2= For both functions defrost / dripping time
0 2
dF 18
Pressure / temperature setpoint to force the ventilation ON during the defrost.
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
Forced defrost
dF 19
Minimum time delay before a forced defrost
0
250
sec
dF 20
Pressure / temperature setpoint for a forced defrost
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
dF 21
Forced defrost differential
0.1
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Defrost operative mode
dF 22
Defrost start-up with 2 circuits
0= Independent
1= If both have reached the necessary requirements
2= If one has reached the necessary requirements
0 2
dF 23
End defrost for two circuits and common ventilation.
0= Independent
1= If both have reached the necessary end defrost requirements
2= If one has reached the necessary end defrost requirements
0 2
Start / stop defrost from analog input
Parameters
description
min
max
udm
resolution
dF 24
Start / stop defrost probe
0= start and stop with condenser temperatur / pressure probe
1= start with evaporator pressure probe / stop with condenser temperatur /
pressure probe
2= start with condenser temperatur / pressure probe / stop with evaporator
pressure probe
3= start and stop with evaporator pressure probe
0 3
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Recovery
Parameters
description
min
max
udm
resolution
rC 1
Recovery modes
0 = not enabled
1 = 2 indipendent circuit
2 = both the circuit in parallel
0 2
rC 2
Delay time delay with step forced off
0
250
Sec
rC 3
Delay time delay with step forced off after the recovery valve activation
0
250
Sec
rC 4
Recovery minimum time
0
250
Min
rC 5
Minimum interval time between the end and the beginning of the next
recovery
0 250 Min
rC 6
Temperature setpoint to disable the recovery
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 7
Temperature differential to restore the recovery
0.1
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 8
Maximum time with recovery disabled (if temperature/pressure within rC6-
rC7)
0 250 Min
Pr1
Password
0
999
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...