1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
28/105
9 TABLE OF THE PARAMETERS
MENU SELECTION
Label
Description
ALL
Shows all the parameters
ST
Shows only the Thermoregulation parameters
CF
Shows only the Configuration parameters
SD
Shows only the Dynamic Setpoint parameters
ES
Shows only the Energy Saving, RTC parameters
CO
Shows only the compressor parameters
US
Shows only the Auxiliary Output parameters
FA
Shows only the Fan Control parameters
Ar
Shows only the Antifreeze Control parameters
DF
Shows only the Defrost parameters
AL
Shows only the Alarm parameters
Thermoregulation
Parameter
Description
min
max
u.m.
Resolution
ST 1
Chiller Setpoint
Allow to modify the setpoint of the unit in chiller mode
ST02
ST03 °C/°F
dec/int
ST 2
Chiller minimum Setpoint
Minimum setpoint limit for ST 1
-30.0
-22
ST01
°C
°F
dec/int
ST 3
Chiller maximum Setpoint
Maximum setpoint limit for ST 1
ST01
70.0
158
°C
°F
dec/int
ST 4
Heat pump setpoint
Allow to modify the setpoint of the unit in heat pump mode
ST05
ST06 °C/°F
dec/int
ST 5
Heat pump minimum Setpoint
Minimum setpoint limit for ST 4
-30.0
-22
ST04
°C
°F
Dec
int
ST 6
Heat pump maximum Setpoint
Maximum setpoint limit for ST 4
ST04
70.0
158
°C
°F
Dec
int
ST 7
Regulation band in chiller mode
0.0
0
25.0
45
°C
°F
Dec
int
ST 8
Regulation band in chiller heat pump
0.0
0
25.0
45
°C
°F
Dec
int
ST 9
Thermoregulation probe selection in chiller
0= Temperature probe NTC for evaporator inlet
1= Temperature probe NTC for evaporator outlet 1
2= Temperature probe NTC for evaporator outlet 2
3= Temperature probe NTC for common evaporator outlet
4= Temperature NTC probe from remote panel 1
5= Temperature NTC probe from remote panel 2
0 5
ST 10
Thermoregulation probe selection in heat pump
0= Temperature probe NTC for evaporator inlet
1= Temperature probe NTC for evaporator outlet 1
2= Temperature probe NTC for evaporator outlet 2
3= Temperature probe NTC for common evaporator outlet
4= Temperature NTC probe from remote panel 1
5= Temperature NTC probe from remote panel 2
6= Temperature probe for water common inlet of the condenser
7= Temperature probe for water inlet of the circuit # 1 condenser
8= Temperature probe for water inlet of the circuit # 2 condenser
9= Temperature probe for water outlet of the circuit # 1 condenser
10= Temperature probe for water outlet of the circuit # 2 condenser
11= Temperature probe for water common otlet of the condenser
ATTENTION
To have the same thermoregulation for chiller and heat pump mode, set the
parameters ST09 and ST10 with the same value
0 11
ST 11
Type of thermoregulation
0= Proportional
1= Neutral zone
2= PI Proportional Integral
0 2
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Display read-out
Parameter
Description
min
max
M. u. Resolution
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...