1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
41.8 AF
R
: P
OWER SUPPLY FREQUENCY ALARM
Label on the display
AFr
(Line frequency alarm)
Origin
The power supply frequency is not equal to the Par. CF81 + tolerance
Reset
Ferquency control parameter adjusted, disabled CF81 = 2, frequency within the tolerance
Restart
Automatic
Icon
Blinking
Action
Alarm relay + buzzer ON
41.9 ALOC: G
ENERIC ALARM WITH STOP REGULATION
Label on the display
ALOC: generic alarm from digital input with stop regulation
Origin
Digital input configured as generic alarm with stop regulation active after the delay in Par. AL43
Reset
Digital input configured as generic alarm with stop regulation not active after the delay in Par.
AL44
Restart
Automatic – It becomes manual after AL42 events/hour (procedura di reset in menù funzioni).
Logged only if manuale
Icon
Blinking
Action
Alarm relay + buzzer ON
REGULATION
Alarm
Alarm relay + buzzer ON
Other loads
OFF
ATTENTION
If during AL44 the alarm stop and start again the AL44 time delay is reloaded.
41.10 ACF1 - ACF2 - ACF3 - ACF4 - ACF5 - ACF6 - ACF7 - ACF8 - ACF9
CONFIGURATION ALARM OF THE UNIT
Label on the display
ACF1
•
Heat pump unit without 4-way valve not configured
•
Defrost wrong parameters (dF22/23)
ACF2
•
Condensing control without probe configuration.
(one probe per circuit with 2 separate circuits, at least 1 probe for common cond.)
•
Fan proportional control algorithm not respected:
FA09 + FA11 + FA12 < FA10
FA12 < FA13
FA07 < FA15 < FA08
•
Fan proportional control algorithm not respected and pump enabled:
FA18 + FA21 + FA20 < FA19
FA21 < FA22
FA16 < FA23 < FA17
•
Fan ON - OFF regulation algorithm not respected:
FA09 < FA10
•
Fan ON - OFF regulation algorithm not respected and pump enabled:
FA18 < FA19
•
With pump and defrost enabled there are no evaporating/condensing probes.
•
With triac regulation (CF68, CF69 = 2) the power supply configuration is Vcc (CF83 = 0)
ACF3
•
Two digital/ analogue inputs configured with the same function or without the necessary
resources (es. compressor # 3 overload but compressor#3 relay not configured)
ACF4
•
CF79 = 1 and its digital input not configured or CF79 = 2 and no external temperature probe
configured.
ACF5
Circuito # 2 not configured but at least one of its resources are present (relay: solenoid pump-
down, heaters, inversion valve, fan condensing ON - OFF, recovery, auxilairy)
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...